NOTES ON WIRING
<br />QS CONTROL LINK
<br />THE QS CONTROL LINK HAS A FREE WIRING TOPOLOGY (DAISY CHAIN, T-TAP, ETC). THE SYSTEM WIRING
<br />ILLUSTRATED BY THIS DRAWING HAS BEEN LAID OUT TO ENSURE APPROPRIATE POWER TO EACH DEVICE. IF FOR
<br />ANY REASON THE SYSTEM IS TO BE WIRED DIFFERENTLY THAN WHAT IS SHOWN, PLEASE CONFIRM ALL DEVICE
<br />POWER REQUIREMENTS ARE MET (PLEASE REFER TO “QS LINK POWER REQUIREMENTS” FOR INDIVIDUAL DEVICE
<br />POWER REQUIREMENTS).
<br />FOR QS CONTROL WIRE LENGTHS TOTALING LESS THAN 500 FT (153 M), USE LUTRON CABLE GRX-CBL-346S (4
<br />CONDUCTOR NON-PLENUM), OR GRX-PCBL-346S (4 CONDUCTOR PLENUM). OTHERWISE USE 2 #18 AWG (1.0 SQ MM) +
<br />2 #22 AWG (0.5 SQ MM) TWISTED AND SHIELDED OR EQUIVALENT (BELDEN #9461). FOR QS CONTROL WIRE LENGTHS
<br />TOTALING UP TO 2,000 FT, USE GRX-CBL-46L (4 CONDUCTOR NON-PLENUM) OR GRX-PCBL-46L (4 CONDUCTOR
<br />PLENUM). TOTAL QS CONTROL WIRE LENGTH MUST NOT EXCEED 2,000 FT (600 M).
<br />ECOSYSTEM BUS/LOOP*
<br />THIS IS A TOPOLOGY-FREE AND POLARITY-FREE WIRING (DAISY-CHAIN, T-TAP, HOME-RUN ETC.). KEEP ALL THE
<br />BALLASTS/MODULES IN ONE ROOM ON THE SAME LOOP WHENEVER POSSIBLE. ECOSYSTEM LOOPS ARE SHOWN ON
<br />THE LIGHTING PLANS. IF THERE IS A DISCREPANCY, AND IF ROOMS ARE WIRED ON A DIFFERENT LOOP THAN THE
<br />ONE SHOWN, LUTRON NEEDS TO BE NOTIFIED AS THIS INFORMATION IS IMPORTANT FOR PROGRAMMING THE
<br />SYSTEM.
<br />USE LUTRON CABLE C-CBL-216-GR1 (2 #16 CONDUCTOR NON-PLENUM) OR C-PCBL-216-CL-1 (2 #16 CONDUCTOR
<br />PLENUM RATED). OTHERWISE USE 2 #16 AWG (1.5 SQ MM) BY OTHERS.
<br />LOOP LENGTH IS LIMITED BY THE WIRE GAUGE USED FOR E1 AND E2 AS FOLLOWS:
<br />WIRE GAUGE MAX LOOP LENGTH
<br />#18 AWG (1.0 SQ MM)
<br />#16 AWG (1.5 SQ MM)
<br />#14 AWG (2.5 SQ MM)
<br />#12 AWG (4 SQ MM)
<br />550 FT (167M)
<br />900 FT (274M)
<br />1,400 FT (426 M)
<br />2,200 FT (670M)
<br />NOTES FOR LED APPLICATIONS
<br />FOR ANY FORWARD/REVERSE PHASE, 3-WIRE, 0-10 V AND SWITCHING LED DRIVERS, PLEASE VERIFY THE NUMBER
<br />OF DRIVERS SUPPORTED ON EACH DEVICE. FOR MORE INFORMATION, PLEASE VISIT LUTRON’S LED CENTER OF
<br />EXCELLENCE (WWW.LUTRON.COM/LEDS).
<br />QS LINK POWER REQUIREMENTS
<br />DEVICE PDUS
<br />QS DEVICES THAT SUPPLY PDU
<br />DIN RAIL POWER SUPPLY +75
<br />MYROOM DIN RAIL POWER SUPPLY +30
<br />QS PLUG-IN POWER SUPPLY, QS J-BOX POWER SUPPLY +8
<br />ENERGI SAVR NODE WITH ECOSYSTEM, ENERGI SAVR NODE WITH
<br />DALI, ENERGI SAVR NODE WITH T-SERIES TUNABLE-WHITE +30
<br />ENERGI SAVR NODE FOR 0–10 V, ENERGI SAVR NODE WITH
<br />SOFTSWITCH, ENERGI SAVR NODE FOR 0–10 V (DIN RAIL), ENERGI
<br />SAVR NODE WITH SOFTSWITCH (DIN RAIL)
<br />+14
<br />ENERGI SAVR NODE PHASE ADAPTIVE (DIN RAIL), 1 A MYROOM DIN
<br />RAIL POWER MODULE SWITCHING, 1 A MYROOM DIN RAIL POWER
<br />MODULE PHASE ADAPTIVE
<br />+4
<br />ENERGI SAVR NODE WITH DALI (DIN RAIL), ENERGI SAVR NODE WITH
<br />ECOSYSTEM (DIN RAIL)+3
<br />QS MOTOR GROUP CONTROLLER (DIN RAIL), HOMEWORKS QS DIN
<br />RAIL POWER MODULES 0
<br />GRAFIK EYE QS (ALL MODELS EXCEPT GRAFIK EYE QS DALI WITH
<br />KNX), QS TIMECLOCK +3
<br />QP2 QUANTUM LIGHTING HUB LINK A : 0
<br />LINKS B,C,D : +33 EACH
<br />QP3 QUANTUM LIGHTING HUB LINKS A,B : +33 EACH
<br />QS DEVICES THAT CONSUME PDU
<br />QS WALLSTATION (SEETOUCH, ARCHITRAVE, SIGNATURE SERIES, QS
<br />PICO, KEYSWITCH, SINGLE COLUMN PALLADIOM), QS SLIDER, GRAFIK
<br />T SLIDER, QS INFRARED (IR) EYE, WALLBOX INPUT CLOSURE
<br />INTERFACE
<br />-1
<br />QS NETWORK INTERFACE, QS DMX INTERFACE, ENERGI SAVR NODE
<br />PROGRAMMING INTERFACE, QS WALLSTATION (DOUBLE COLUMN
<br />PALLADIOM)
<br />-2
<br />QS SENSOR MODULE (QSM), NOT INCLUDING ATTACHED WIRED
<br />SENSORS (SEE SECTION BELOW FOR MORE INFORMATION), QS
<br />CONTACT CLOSURE INTERFACE, PALLADIOM ROOM THERMOSTAT
<br />-3
<br />GUESTROOM CONTROL UNIT -8
<br />SENSORS & DEVICES THAT CONSUME PDUS WHEN WIRED TO A QSM
<br />LUTRON DAYLIGHT SENSOR, LUTRON INFRARED (IR) RECEIVER, PICO
<br />WIRED CONTROLLER -0.5
<br />ECOSYSTEM WALLSTATION -1
<br />LOS C SERIES OCCUPANCY SENSOR, HIGH BAY OCCUPANCY SENSOR -2
<br />ONSITE PRE-WIRE VISIT
<br />(LSC-PREWIRE)
<br />AN ONSITE VISIT WITH THE ELECTRICAL CONTRACTOR TO DISCUSS LOGISTICAL CONSTRUCTION CONSIDERATIONS INCLUDING THE
<br />WIRING AND MOUNTING OF SYSTEM DEVICES, THE CONSTRUCTION SCHEDULE, AND LUTRON DOCUMENTATION. QUANTITY DICTATES
<br />THE NUMBER OF VISITS PURCHASED.
<br />SYSTEM & NETWORK
<br />INTEGRATION
<br />CONSULTATION
<br />(LSC-INT-VISIT)
<br />A CONSULTATIVE VISIT WITH THIRD PARTY INTEGRATORS TO CONFIRM THE SPECIFIED SEQUENCE OF OPERATION AND DISCUSS
<br />INTEGRATION PROCEDURES NEEDED IN ORDER TO INTEGRATE WITH THE LUTRON EQUIPMENT. THIS MAY INCLUDE ANY OF THE
<br />FOLLOWING THIRD PARTY SYSTEMS: BMS, BAS, IT, NON-LUTRON SHADES, BACNET, AV, OR ENERGY DASHBOARDS.
<br />SENSOR LAYOUT &
<br />TUNING
<br />(LSC-SENS-LT)
<br />LUTRON WILL TAKE RESPONSIBILITY FOR LUTRON-PROVIDED SENSOR PLACEMENT AND PERFORMANCE BY CREATING SENSOR
<br />LAYOUTS AND COORDINATING SENSOR PLACEMENT BEFORE AND AFTER INSTALLATION. ONCE THE BUILDING IS OCCUPIED, LUTRON
<br />WILL RETURN UP TO TWO TIMES TO PERFORM SENSOR FINE-TUNING.
<br />AFTER HOURS STARTUP
<br />(LSC-AH-SU)
<br />STARTUP PROVIDED BETWEEN THE HOURS OF 5:00PM – 7:00AM, MONDAY - FRIDAY. THIS SCOPE OF WORK DOES NOT INCLUDE
<br />HOLIDAY OR WEEKEND WORK. ADDITIONAL FEES MAY APPLY FOR WORK TO BE COMPLETED ON WEEKENDS (FRIDAY 5:00PM –
<br />MONDAY 7:00AM).
<br />ONSITE SCENE & LEVEL
<br />TUNING
<br />(LSC-AF-VISIT)
<br />AN ONSITE VISIT WITH THE SPECIFIER OR CUSTOMER REPRESENTATIVE TO REVIEW THE DESIGN INTENT, FINE-TUNE THE SCENE
<br />LEVEL PROGRAMMING, AND MAKE ADJUSTMENTS TO TIMECLOCKS.
<br />ONSITE
<br />PERFORMANCE-VERIFIC
<br />ATION WALKTHROUGH
<br />(LSC-WALK)
<br />AN ONSITE WALKTHROUGH WITH FACILITY REPRESENTATIVES OR PROJECT COMMISSIONING AGENTS TO DEMONSTRATE THAT THE
<br />SYSTEM FUNCTIONALITY MEETS THE DESIGN INTENT. THIS MAY INCLUDE ANY OF THE FOLLOWING ONSITE ACTIVITIES –
<br />CONSULTATION/TRAINING DEMOS, FUNCTIONAL TESTING ASSISTANCE, OR INVENTORY OF LUTRON EQUIPMENT.
<br />SYSTEM
<br />PERFORMANCE-VERIFIC
<br />ATION
<br />DOCUMENTATION
<br />(LSC-SPV-DOC)
<br />COMPLETION OF DOCUMENTATION WHICH PROVIDES PERFORMANCE VERIFICATION CERTIFYING THE LUTRON EQUIPMENT HAS
<br />BEEN THOROUGHLY TESTED. IT SUPPORTS THE DOCUMENTATION REQUIREMENTS OF MANY BUILDING STANDARDS.
<br />TITLE 24 ACCEPTANCE
<br />TEST VISIT
<br />(LSC-SPV-DOC-T24)
<br />ACCEPTANCE TESTING BY A LUTRON CERTIFIED LIGHTING CONTROL ACCEPTANCE TEST TECHNICIAN (CLCATT) TO FULFILL THE
<br />REQUIRED TITLE 24 INTERIOR LIGHTING CONTROL TESTS.
<br />CUSTOMER-SITE
<br />SOLUTION TRAINING
<br />(LSC-TRAINING-SP)
<br />A VISIT TO TEACH SYSTEM USERS HOW TO OPERATE AND MAINTAIN THE LIGHTING CONTROL SYSTEM.
<br />SYSTEM OPTIMIZATION
<br />(LSC-SYSOPT-SP)
<br />AN ONSITE CONSULTATIVE VISIT TO IDENTIFY AND IMPLEMENT LIGHTING CONTROL ADJUSTMENTS TO SAVE ADDITIONAL ENERGY
<br />AND CREATE A MORE PRODUCTIVE WORK ENVIRONMENT.
<br />ENHANCED SILVER
<br />(LSC-E8S)
<br />YEARS 1-2 - 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A FIRST-AVAILABLE RESPONSE
<br />TIME; YEARS 3-5 - 50% PARTS ONLY COVERAGE; YEARS 6-8 - 25% PARTS ONLY COVERAGE.
<br />ENHANCED GOLD
<br />(LSC-E8G)
<br />YEARS 1-2 - 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A 72-HOUR RESPONSE TIME AND
<br />AN ANNUAL (1-DAY) SCHEDULED PREVENTIVE MAINTENANCE VISIT; YEARS 3-5 - 50% PARTS ONLY COVERAGE; YEARS 6-8 - 25% PARTS
<br />ONLY COVERAGE.
<br />ENHANCED PLATINUM
<br />(LSC-E8P)
<br />YEARS 1-2 - 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A 24-HOUR RESPONSE TIME AND
<br />AN ANNUAL (1-DAY) SCHEDULED PREVENTIVE MAINTENANCE VISIT; YEARS 3-5 - 50% PARTS ONLY COVERAGE; YEARS 6-8 - 25% PARTS
<br />ONLY COVERAGE.
<br />SILVER TECHNOLOGY
<br />SUPPORT PLAN
<br />(LSC-SILV-IW)
<br />AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A
<br />FIRST-AVAILABLE ONSITE OR REMOTE RESPONSE TIME.
<br />GOLD TECHNOLOGY
<br />SUPPORT PLAN
<br />(LSC-GOLD-IW)
<br />AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON LABOR WITH A 72-HOUR ONSITE OR
<br />REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTIVE MAINTENANCE VISIT EACH YEAR.
<br />PLATINUM
<br />TECHNOLOGY
<br />SUPPORT PLAN
<br />(LSC-PLAT-IW)
<br />AN ANNUAL SERVICE PLAN THAT COVERS 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR WITH A 24-HOUR
<br />ONSITE OR REMOTE RESPONSE TIME. ALSO INCLUDES AN ANNUAL (1-DAY) SCHEDULED PREVENTIVE MAINTENANCE VISIT EACH
<br />YEAR.
<br />PREVENTIVE
<br />MAINTENANCE VISIT(S)
<br />(LSC-SCH-MAINT)
<br />SCHEDULED MAINTENANCE VISIT TO PERFORM PREVENTIVE MAINTENANCE, MINOR PROGRAMMING, AND CONDUCT SYSTEM
<br />TRAININGS. QUANTITY IS IN ADDITION TO ANY YEARLY VISITS SPECIFIED WITH AN ENHANCED WARRANTY OR TECHNOLOGY
<br />SUPPORT PLAN.
<br />LUTRON SERVICES
<br />QTY
<br />SERVICE TITLE
<br />(MODEL NUMBER)SERVICE DESCRIPTION
<br />THE QUANTITY OF SERVICES BELOW ARE TO BE INCLUDED AS PART OF THIS PROJECT'S SCOPE OF WORK AND SPECIFIED INTO THE WRITTEN SPEC
<br />DOCUMENTS
<br />PRE-STARTUP SERVICES
<br />STARTUP SUPPORT SERVICES
<br />(THESE SERVICES ARE ADDITIONAL TO YOUR SPECIFIED STARTUP BASED ON YOUR REQUIREMENTS)
<br />POST-STARTUP SERVICES
<br />MAINTENANCE & SUPPORT SERVICES
<br />1
<br />COMMERCIAL SYSTEMS
<br />2-YEAR LIMITED
<br />WARRANTY
<br />(LSC-B2)
<br />A 2-YEAR SYSTEM WARRANTY PROVIDING 100% REPLACEMENT PARTS AND 100% LUTRON DIAGNOSTIC LABOR COVERAGE WITH A
<br />FIRST-AVAILABLE RESPONSE TIME.
<br />PLEASE GO TO WWW.LUTRON.COM/SERVICES FOR FURTHER INFORMATION.
<br />FOR MORE INFORMATION CONTACT:
<br />MANUEL ABELLO
<br />(484) 221-5539
<br />mabello@lutron.com
<br />1423
<br />A
<br />C
<br />B
<br />1423
<br />A
<br />C
<br />SHEET NUMBER
<br />TITLE
<br />Approved
<br />Checked
<br />Drawn
<br />Job Number
<br />ISSUE CHART
<br />CONSULTANTS
<br />KEYPLAN
<br />PROJECT
<br />B
<br />FIRM CERTIFICATION C.A #6057
<br />JOHN MOULDER P.E: #33200
<br />CARLOS E. JIMENEZ P.E: #47923
<br />JOHN J. PETERS RCDD #193108R
<br />BR+A CONSULTING ENGINEERS
<br />2600 DOUGLAS ROAD, SUITE 1100
<br />CORAL GABLES, FL 33134
<br />t. 305.529.1515
<br />THORNTON TOMASETTI
<br />101 NE THIRD AVENUE, SUITE 1170
<br />FORT LAUDERDALE, FL 3330`
<br />f.954.903.9300
<br />f 954.903 9301
<br />ESI CONSULTING ENGINEERS, INC
<br />1315 NW 98TH CT.
<br />UNIT 15, DORAL, FL 33172
<br />t. 305.418.9177 t 305.418.9178
<br />HVAC
<br />STRUCTURAL ENGINEERS
<br />ELEC + PLUM + FPRO + TECH
<br />INMAN FOODSERICE GROUP
<br />1330 CORAL WAY
<br />SUITE 310
<br />MIAMI, FL 33145
<br />FOOD SERVICE
<br />PE
<br />R
<br />M
<br />I
<br />T
<br />
<br />S
<br />E
<br />T
<br />
<br />1
<br />2
<br />.
<br />0
<br />6
<br />.
<br />1
<br />8
<br />FIRM CERTIFICATION C.A #26243
<br />IGOR F. GONZALEZ P.E: #56098
<br />1 2 /1 1 /2 0 1 8 4 :1 8 :5 1 P M
<br />C :\_R e v i t \E L E C - G A T E W A Y - v 2 0 1 8 _j p e r e z @ b r p l u s a .c o m .r v t
<br />E50-03
<br />LIGHTING CONTROL
<br />RISER 2
<br />Checker
<br />Author
<br />810495.000
<br />Approver
<br />SIB -GATEWAY
<br />PARK
<br />Copyright © 2018 Perkins+Will
<br />PROJECT ADDRESS:
<br />151 Sunny Isles Blvd
<br />Sunny Isles Beach, FL
<br />33160
<br />2800 Ponce De Leon Blvd
<br />Suite 1300
<br />Coral Gables, FL 33134
<br />t 305.569.1333
<br />f 305.569.1334
<br />www.perkinswill.com
<br />NO.ISSUE DATE
<br />PERMIT SET 12.06.2018
|