ACCESS CONTROL SYSTEM SYMBOLSELECTRONIC SAFETY AND SECURITY ABBREVIATIONS
<br />CR
<br />RX
<br />ACP
<br />SECURITY COMM SYSTEMS SYMBOLS
<br />AA
<br />EL
<br />TN
<br />ELR
<br />PP
<br />PB
<br />PS
<br />TH
<br />ADO
<br />ML
<br />DC
<br />CARD READER
<br />PIR REQUEST-TO-EXIT
<br />ACCESS CONTROL PANEL -SHOWN FOR COORDINATION ONLY
<br />DOOR CONTACT
<br />AUDIBLE ALARM
<br />OPTICAL TURNSTILE
<br />ELECTRIFIED LOCK
<br />AUTOMATIC DOOR OPERATOR
<br />MAGNETIC LOCK
<br />ELECTRIC LATCH RETRACTION
<br />ADO PUSH PLATE
<br />DOOR RELEASE PUSH BUTTON
<br />LOCAL LOCK POWER SUPPLY
<br />ELECTRIC TRANSFER HINGE
<br />JB 8x8x6 NEMA 1 JUNCTION BOX WITH SCREW COVER
<br />BL BLUE LIGHT PHONE CALL POINT
<br />ES ELECTRIC STRIKE
<br />I/O ACS INPUT/OUTPUT PANEL
<br />VI VIDEO INTERCOM DOOR STATION
<br />IC VOICE ONLY INTERCOM DOOR STATION
<br />SECURITY RACEWAY REQUIREMENTS GENERAL NOTES:
<br />1.SECURITY DETAILS ARE DIAGRAMMATIC AND INTENDED FOR OWNING THE SCOPE OF THE
<br />SYSTEMS AND REQUIREMENTS, ALL FINAL INSTALLATIONS SHALL BE BASED ON APPROVED
<br />SHOP DRAWINGS.
<br />2.CONTRACTOR SHALL PROVIDE DETAILED SHOP DRAWINGS INDICATING FINAL CABLING AND
<br />CONDUIT SIZES AS COORDINATED WITH APPROVED SHOP DRAWINGS PRIOR TO ROUGH-IN
<br />3.PRIOR TO ROUGH-IN, CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS, RCPs,
<br />ELEVATIONS AND SCHEDULES FOR ALL FINAL MOUNTING HEIGHTS AND LOCATIONS.
<br />4.THE CONTRACTOR SHALL PROVIDE DETAILED COORDINATION DRAWINGS FOR SUBMITTAL TO
<br />ENSURE THAT ALL SIZES, AND SYSTEMS ARE COORDINATED WITH ALL TRADES AND
<br />SYSTEMS.
<br />5.INSTALLATION OF ALL RACEWAYS SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH
<br />REFERENCED STANDARDS NOTED IN SPECIFICATIONS AND CONTRACT DOCUMENTS HEREIN.
<br />A AMPERES
<br />AC ALTERNATING CURRENT
<br />ACS ACCESS CONTROL SYSTEM
<br />ACP ACCESS CONTROL PANEL
<br />A/D ANALOG TO DIGITAL CONVERSION
<br />ADA AMERICANS WITH DISABILITIES ACT
<br />ADO AUTOMATIC DOOR OPERATOR
<br />AER AERIAL
<br />AFF ABOVE FINISHED FLOOR
<br />AIA AMERICAN INSTITUTE OF ARCHITECTS
<br />AM AMPLITUDE MODULATION
<br />ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
<br />AWG AMERICAN WIRE GAUGE
<br />BDF BUILDING DISTRIBUTION FRAME
<br />BEF BUILDING ENTRANCE FACILITY
<br />BICSI BUILDING INDUSTRY CONSULTING SERVICES
<br />BTU BRITISH THERMAL UNIT
<br />C CONDUIT
<br />CATV CABLE TELEVISION
<br />CB CIRCUIT BREAKER
<br />CCTV CLOSED CIRCUIT TELEVISION
<br />CER COMPUTER EQUIPMENT ROOM
<br />CKT CIRCUIT
<br />CL CENTER LINE
<br />CLG CEILING
<br />COND CONDUCTOR
<br />CPU CENTRAL PROCESSING UNIT
<br />CU COPPER
<br />D/A DIGITAL TO ANALOG CONVERSION
<br />DB DECIBEL
<br />DC DIRECT CURRENT
<br />DGP DATA GATHERING PANEL
<br />DVR DIGITAL VIDEO RECORDER
<br />DWG DRAWING(S)
<br />EBC EQUIPMENT BONDING CONDUCTOR
<br />EC ELECTRICAL CONTRACTOR
<br />EIA ELECTRONICS INDUSTRY ASSOCIATION
<br />ELEC ELECTRICAL
<br />EM EMERGENCY
<br />EMI ELECTROMAGNETIC INTERFACE
<br />EMR ELEVATOR MACHINE ROOM
<br />EMT ELECTRICAL METALLIC TUBING
<br />EOLR END-OF-LINE RESISTOR
<br />FA FIRE ALARM
<br />FCC FEDERAL COMMUNICATIONS COMMISSION
<br />FO FIBER OPTIC
<br />FREQ FREQUENCY
<br />FTP FOIL TWISTED PAIR
<br />G GROUND
<br />GHz GIGAHERTZ
<br />GND GROUND
<br />HH HANDHOLE
<br />Hz HERTZ
<br />IDF INTERMEDIATE DISTRIBUTION FRAME
<br />IDS INTRUSION DETECTION SYSTEM
<br />IDP INTRUSION DETECTION PANEL
<br />IEEE INTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
<br />I/O INPUT/ OUTPUT
<br />JB JUNCTION BOX
<br />KHz KILOHERTZ
<br />LAN LOCAL AREA NETWORK
<br />LED LIGHT EMITTING DIODE
<br />LV LOW VOLTAGE
<br />MAX MAXIMUM
<br />MDF MAIN DISTRIBUTION FRAME
<br />MER MECHANICAL EQUIPMENT ROOM
<br />MIN MINIMUM
<br />MISC MISCELLANEOUS
<br />MTD MOUNTED
<br />MUX MULTIPLEXER
<br />N NEUTRAL
<br />NC NORMALLY CLOSED
<br />NEC NATIONAL ELECTRIC CODE
<br />NESC NATIONAL ELECTRIC SAFETY CODE
<br />NIC NOT IN CONTRACT
<br />NO NORMALLY OPEN
<br />No NUMBER
<br />NRTL NATIONALLY RECOGNIZED TESTING LABORATORY
<br />NTS NOT TO SCALE
<br />NVR NETWORK VIDEO RECORDER
<br />OC ON CENTER
<br />OD OUTSIDE DIAMETER
<br />OPD OVERCURRENT PROTECTION DEVICE
<br />OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
<br />OSP OUTSIDE PLANT
<br />PA PUBLIC ADDRESS
<br />PB PULL BOX
<br />PBX PRIVATE BRANCH EXCHANGE
<br />PIR PASSIVE INFRA-RED
<br />POTS PLAIN OLD TELEPHONE SERVICE
<br />PP PATCH PANEL
<br />PS POWER SUPPLY
<br />PSIM PHYSICAL SECURITY INFORMATION MANAGEMENT
<br />PTZ PAN-TILZ-ZOOM
<br />PVC POLYVINYL CHLORIDE
<br />RX REQUEST TO EXIT
<br />SC SECURITY CONTRACTOR
<br />SI SYSTEM INTERNATIONAL
<br />SL SLEEVE
<br />SMS SECURITY MANAGEMENT SYSTEM
<br />SP SERVICE PROVIDER
<br />SPD SURGE PROTECTION DEVICE
<br />SPG SINGLE-POINT GROUND
<br />STP SHIELDED TWISTED PAIR
<br />SW SWITCH-POE (LOCAL AREA NETWORK)
<br />SYS SYSTEM
<br />TC TELECOMMUNICATIONS CONTRACTOR
<br />TEL TELEPHONE
<br />TELCO TELEPHONE COMPANY
<br />TGB TELECOMMUNICATIONS GROUNDING BUSBAR
<br />TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION
<br />TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
<br />TO TELECOMMUNICATIONS OUTLET
<br />TR TELECOMMUNICATIONS ROOM
<br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
<br />TYP TYPICAL
<br />UG UNDERGROUND
<br />UL UNDERWRITERS LABORATORIES
<br />UPS UNINTERRUPTIBLE POWER SUPPLY
<br />UTP UNSHIELDED TWISTED PAIR
<br />VMS VIDEO MANAGEMENT SYSTEM
<br />WF WALL FIELD
<br />WS WORKSTATION
<br />INTRUSION DETECTION SYSTEM SYMBOLS
<br />KP
<br />MS
<br />DB
<br />ICP
<br />WR
<br />KEYPAD
<br />MOTION SENSOR
<br />DURESS BUTTON
<br />WIRELESS RECIEVER
<br />INTRUSION CONTROL PANEL -SHOWN FOR
<br />COORDINATION ONLY
<br />DEVICES PROVIDED BY DIVISION 08.
<br />SHOWN FOR REFERENCE ONLY
<br />CCTV SYSTEMS LEGEND
<br />FIXED, VARI-FOCAL DOME CCTV CAMERA
<br />PANORAMIC, 180° DOME CCTV CAMERA
<br />PANORAMIC, 360° DOME CCTV CAMERA
<br />VI VIDEO INTERCOM MASTER STATION
<br />D
<br />D
<br />M
<br />NVR NETWORK VIDEO RECORDER
<br />CEILING MOUNTED CAMERAS
<br />#SEQUENTIAL CAMERA NUMBER. TYP.
<br />FIXED, VARI-FOCAL DOME CCTV CAMERA
<br />PANORAMIC, 180° DOME CCTV CAMERA
<br />PANORAMIC, 360° DOME CCTV CAMERA
<br />WALL/POLE MOUNTED CAMERAS
<br />#SEQUENTIAL CAMERA NUMBER. TYP.
<br />ELECTRONIC SAFETY AND SECURITY GENERAL NOTES
<br />1423
<br />A
<br />C
<br />B
<br />1423
<br />A
<br />C
<br />SHEET NUMBER
<br />TITLE
<br />Approved
<br />Checked
<br />Drawn
<br />Job Number
<br />ISSUE CHART
<br />CONSULTANTS
<br />KEYPLAN
<br />PROJECT
<br />B
<br />FIRM CERTIFICATION C.A #6057
<br />ERIK S WALKER P.E: #63929
<br />JOHN MOUDLER P.E: #33200
<br />CARLOS E. JIMENEZ P.E: #47923
<br />RICARDO DURAN P.E: #64768
<br />GLEN R. SEILER P.E: #83347
<br />BR+A CONSULTING ENGINEERS
<br />2600 DOUGLAS ROAD, SUITE 1100
<br />CORAL GABLES, FL 33134
<br />THORNTON TOMASETTI
<br />101 NE THIRD AVENUE, SUITE 1170
<br />FORT LAUDERDALE, FL 3330`
<br />f.954.903.9300
<br />f 954.903 9301
<br />ESI CONSULTING ENGINEERS, INC
<br />1315 NW 98TH CT.
<br />UNIT 15, DORAL, FL 33172
<br />t. 305.418.9177
<br />t 305.418.9178
<br />HVAC
<br />STRUCTURAL ENGINEERS
<br />ELECTRICAL + PLUMBING
<br />INMAN FOODSERICE GROUP
<br />1330 CORAL WAY
<br />SUITE 310
<br />MIAMI, FL 33145
<br />FOOD SERVICE
<br />PE
<br />R
<br />M
<br />I
<br />T
<br />
<br />S
<br />E
<br />T
<br />
<br />1
<br />2
<br />.
<br />0
<br />6
<br />.
<br />1
<br />8
<br />1 2 /4 /2 0 1 8 8 :0 7 :3 7 A M
<br />C :\_R e v i t \T E C H - G A T E W A Y - v 2 0 1 8 _a v i l l a n u e v a C B Y X V .r v t
<br />SE00-01
<br />SECURITY LEGEND
<br />JJP
<br />AMV
<br />810495.000
<br />JJP
<br />SIB -GATEWAY
<br />PARK
<br />Copyright © 2018 Perkins+Will
<br />PROJECT ADDRESS:
<br />151 Sunny Isles Blvd
<br />Sunny Isles Beach, FL
<br />33160
<br />2800 Ponce De Leon Blvd
<br />Suite 1300
<br />Coral Gables, FL 33134
<br />t 305.569.1333
<br />f 305.569.1334
<br />www.perkinswill.com
<br />48 TERMINALS, CONNECTORS, DEVICES, CIRCUITS, CABLES, AND CABLE TERMINATIONS SHALL BE CLEARLY,
<br />LOGICALLY, AND PERMANENTLY MARKED DURING INSTALLATION. ALL EQUIPMENT AND CONDUITS SHALL BE
<br />IDENTIFIED.
<br />49 ALL WIRING AND ELECTRICAL CIRCUITS SHALL BE NUMERICALLY IDENTIFIED AT BOTH ENDS AS REQUIRED BY
<br />THE CONTRACT DOCUMENTS. EACH SYSTEM CONDUIT JUNCTION BOX, PULL BOX, OR ELECTRICAL ENCLOSURE
<br />(FROM TERMINATION TO TERMINATION) CONTAINING SYSTEM CONDUCTORS, INCLUDING INITIATING DEVICE,
<br />NOTIFICATION APPLIANCE, AND AUXILIARY FUNCTION CIRCUITS.
<br />50 AC POWER CONDUCTORS OR GROUNDING CONDUCTORS SHALL BE UNIQUELY AND PERMANENTLY LABELED
<br />WITH A NUMBERED TAG, LABEL OR STENCIL. LABEL SYSTEM PROPOSED BY THE CONTRACTOR SHALL BE
<br />TYPEWRITTEN AND APPROVED BY OWNER OR THEIR AUTHORIZED REPRESENTATIVE.
<br />51 ENCLOSURES, CABINETS, HOUSINGS, CONSOLES, POWER SUPPLY ENCLOSURES, CONTROL AND TERMINAL
<br />CABINETS, CONTROL UNITS, WIRING GUTTERS AND OTHER COMPONENT HOUSINGS, BOXES AND FITTINGS OR
<br />EVERY PRODUCT DESCRIPTION, COLLECTIVELY REFERRED TO AS ENCLOSURES, SHALL BE SO FORMED AND
<br />ASSEMBLED AS TO BE STURDY AND RIGID.
<br />52 ENCLOSURES, CABINETS, HOUSINGS, BOXES AND FITTINGS OR EVERY PRODUCT DESCRIPTION HAVING HINGED
<br />DOORS OR REMOVABLE COVERS AND WHICH CONTAIN CIRCUITS, OR THE INTEGRATED SECURITY SYSTEMS
<br />AND IT'S POWER SUPPLIES SHALL BE PROVIDED WITH COVER OPERATED, CORROSION-RESISTANT TAMPER
<br />SWITCHES. ALL EQUIPMENT SHALL BE PROPERLY ATTACHED AND HELD FIRMLY IN PLACE. FASTENINGS AND
<br />SUPPORTS SHALL BE ADEQUATE TO SUPPORT LOADS WITH MINIMUM SAFETY FACTOR OF THREE (3). ALL
<br />MEANS OF EQUIPMENT AND CONDUIT SUPPORT SHALL BE APPROVED.
<br />53 ALL WIRING SHALL BE RUN PERPENDICULAR OR PARALLEL TO THE FLOOR PLANE, WITH ALL BENDS MADE AT
<br />NEAT RIGHT ANGLES.
<br />54 ALL WIRING WITHIN THE CABINET SHALL BE PERMANENTLY ATTACHED USING SPIRAL WRAP TUBING AND NYLON
<br />WIRE TIES WITH MECHANICAL (I.E.: SCREWS, RIVETS) FASTENERS. THE USE OF SELF-ADHESIVE FASTENERS
<br />INSIDE THE CABINET(S) IS SPECIFICALLY PROHIBITED.
<br />55 ALL ENCLOSURE PENETRATIONS SHALL BE FROM THE BOTTOM UNLESS THE SYSTEM DESIGN REQUIRES
<br />PENETRATIONS FROM OTHER DIRECTIONS. PENETRATIONS OF INTERIOR ENCLOSURES INVOLVING
<br />TRANSITIONS OF CONDUIT FROM INTERIOR TO EXTERIOR, AND ALL PENETRATIONS ON EXTERIOR ENCLOSURES
<br />SHALL BE SEALED WITH RUBBER SILICONE SEALANT TO PRECLUDE THE ENTRY OF WATER. THE TERMINATOR
<br />SHALL BE FILLED WITH AN APPROVED SEALANT AS RECOMMENDED BY THE CABLE MANUFACTURER AND IN
<br />SUCH A MANNER THAT THE CABLE IS NOT DAMAGED.
<br />56 ALL WIRING WITHIN THE CABINET SHALL BE NEATLY ROUTED IN HORIZONTAL AND VERTICAL CHANNELS
<br />PARALLEL TO THE CABINET'S SIDES AND THE INTERIOR TERMINAL STRIPS. WIRING SHALL NOT BE ROUTED
<br />OVER CIRCUIT BOARDS, TRANSFORMERS, OR TERMINAL STRIPS. AS GENERAL PRACTICE, RUN ALL POWER
<br />CABLES, CONTROL CABLES, AND HIGH-LEVEL CABLES ON ONE SIDE OF AN EQUIPMENT CABINET. RUN ALL
<br />OTHER CABLES ON THE OPPOSITE SIDE OF AN EQUIPMENT CABINET. THE CONTRACTOR SHALL MAINTAIN A
<br />MINIMUM OF A TWELVE (12) INCH DISTANCE BETWEEN ALL PARALLEL RUNS OF AC ELECTRICAL POWER AND
<br />LOW VOLTAGE CONDUIT OR LOW VOLTAGE WIRING.
<br />57 NO CONDUIT SHALL BE LESS THAN 3/4" IN DIAMETER UNLESS DESIGNATED BY THESE SPECIFICATIONS AND/OR
<br />PLANS. A PULL STRING SHALL BE INCLUDED IN EACH INDIVIDUAL CONDUIT RUN.
<br />58 PROVIDE TESTING AND VERIFY THAT ALL SYSTEM CABLING AND FIELD WIRING IS FREE OF SHORTS, GROUNDS,
<br />OPENS, HIGH RESISTANCE, AND OTHER FAULTS PRIOR TO TERMINATION TO DEVICES AND EQUIPMENT. THE
<br />CONTRACTOR SHALL PROVIDE A DETAILED REPORT OF THE TEST TO OWNER'S SECURITY AND ITS
<br />AUTHORIZED REPRESENTATIVE.
<br />59 ALL CONDUITS SHALL BE IN INSTALLED IN ACCORDANCE WITH NFPA 70, THE NATIONAL ELECTRICAL CODE
<br />(NEC), AMERICAN DISABILITY ACT (ADA) AND THE CONTRACT DOCUMENTS.
<br />60 ALL CONDUIT ROUTES SHALL BE SO DESIGNED TO ENSURE THAT ALL LOW VOLTAGE WIRE AND CONDUIT
<br />MAINTAIN THE REQUIRED MINIMUM OF TWELVE-INCH (12") DISTANCE SEPARATION FROM ANY OPEN
<br />CONDUCTORS OF POWER, OR CLASS 1 CIRCUIT AND SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX
<br />OR RACEWAY CONTAINING THESE CONDUCTORS, AS PER NFPA 70, THE NATIONAL ELECTRICAL CODE (NEC).
<br />61 THE ELECTRICAL CONTRACTOR SHALL AVOID CONDUIT RUNS PARALLEL TO ALL AC ELECTRICAL POWER. ANY
<br />LOW VOLTAGE CONDUIT OR LOW VOLTAGE WIRING THAT CROSSES OVER AC ELECTRICAL POWER SHALL BE AT
<br />A 90-DEGREE ANGLE.
<br />62 ALL CONDUITS, RACEWAYS, AND OTHER ASSOCIATED ITEMS RELATED TO THE SYSTEM INSTALLED, SHALL NOT
<br />OBSTRUCT ANY PORTION OF A WINDOW, DOORWAY, STAIRWELL, OR PASSAGEWAY AND SHALL NOT INTERFERE
<br />WITH THE OPERATION OF ANY EXISTING MECHANICAL OR ELECTRICAL EQUIPMENT.
<br />63 ALL BACK BOXES PROVIDED FOR RECESSED CEILING INSTALLATION SHALL INCLUDE ADEQUATE ACCESS AND
<br />SHALL BE RATED FOR USE IN CEILINGS AND SHALL MEET OR EXCEED ALL APPLICABLE NATIONAL AND LOCAL
<br />ELECTRICAL CODES.
<br />64 ALL JUNCTION BOXES DEFINED BY THE RECORD SPECIFICATION MAY BE CONCEALED BUT MUST REMAIN
<br />ACCESSIBLE FOR SERVICE AND TESTING. SECURITY JUNCTIONS BOXES MAY BE RECESSED INTO WALL OR
<br />CEILING.
<br />65 ALL JUNCTION BOXES AND SMALL DEVICE ENCLOSURES BELOW THE CEILING AND EASILY ACCESSIBLE TO
<br />EMPLOYEES OR THE PUBLIC SHALL BE TAMPER PROOF, MONITORED, AND COVERED WITH SUITABLE COVER
<br />PLATE. ALL JUNCTION BOXES ABOVE CEILING LEVEL IN OCCUPIED AREAS OF THE BUILDING SHALL NOT BE
<br />CONSIDERED TO BE EASILY ACCESSIBLE. ALL LOCATIONS CONTAINING SECURITY SYSTEM COMPONENTS
<br />UNDER THESE CONDITIONS SHALL INCORPORATE SECURE TAMPERPROOF SCREWS OR SIMILAR APPROVED
<br />DEVICES.
<br />66 ALL SYSTEM CABLING PROVIDED, AS PART OF THIS SYSTEM SHALL BE INSTALLED IN DEDICATED CONDUIT
<br />RACEWAYS, WHICH ARE NOT USED FOR ANY OTHER PURPOSE, FUNCTION, OR SYSTEM.
<br />67 CONDUIT SHALL BE CONCEALED IN ALL FINISHED AREAS. EXPOSED CONDUIT IS PERMITTED IN ELECTRICAL,
<br />MECHANICAL AND UNFINISHED AREAS ONLY AS DETERMINED BY THE ARCHITECT PRIOR TO INSTALLATION.
<br />68 ANY RUN OF EXPOSED CONDUIT SHALL BE PARALLEL OR AT A RIGHT ANGLE TO THE BUILDING LINES.
<br />69 THE SECURITY CONTRACTOR SHALL COORDINATE WITH ELECTRICAL CONTRACTOR TO PROVIDE CONSTANT
<br />120VAC TO ALL SECURITY EQUIPMENT ROOMS.
<br />70 ALL DEVICES GENERATING RADIO FREQUENCIES SHALL BE CERTIFIED TO COMPLY WITH THE REQUIREMENTS
<br />OF FCC PART 15 AND LABELED AS SET FORTH IN FCC PART 15.
<br />71 CONTRACTOR SHALL TAKE ALL OTHER PRECAUTIONS IN ACCORDANCE WITH MANUFACTURER'S
<br />RECOMMENDATIONS TO PREVENT ELECTROMAGNETIC INTERFERENCE WITH DATA TRANSMISSIONS.
<br />72 NON-SECURITY SYSTEM WIRING SHALL NOT SHARE SECURITY CONDUIT.
<br />73 THE SECURITY SYSTEM NETWORK SHALL COMMUNICATE WITH THE SYSTEM CONTROL WORKSTATIONS
<br />THROUGH INDUSTRY STANDARD NETWORK SWITCHES AND ROUTERS AND SHALL NOT BE REQUIRED TO
<br />RESIDE ON THE SAME SUBNET, AS THE INFORMATION TECHNOLOGY NETWORK.
<br />74 THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE CONTRACTOR OF DIVISION 08 700-DOOR
<br />HARDWARE.
<br />75 ALL ELECTRIFIED DOORS SHALL BE OPERATIONAL FROM THE INSIDE WITHOUT USE OF A KEY OR ANY SPECIAL
<br />KNOWLEDGE OR EFFORT PER NFPA 101.
<br />76 THE SECURITY CONTRACTOR SHALL COORDINATE WITH THE DOOR HARDWARE CONTRACTOR AS TO
<br />INTERCONNECTION OF ALL INPUT TRIGGERS FOR RELEASE OF ELECTRICAL LOCKING HARDWARE AND
<br />CONTACT OUTPUTS REQUIRED TO MONITOR DOOR RELATED ALARM POINTS.
<br />77 ALL CAMERA CABLING SHALL BE CONCEALED AND PROTECTED IN A RIGID ENCASEMENT, CONDUIT, ARMORED
<br />FLEX, OR SIMILAR APPROVED PASSAGES. CAMERA PLACEMENTS IN THE FIELD ARE FORBIDDEN TO HAVE
<br />UNPROTECTED AND EXPOSED CONNECTORS, POWER CABLE, AND VIDEO FEEDS. INTEGRATED ARMATURES
<br />THAT PASS THE CABLING FROM THE CAMERA TO THE WALL / JUNCTION BOX WITHOUT EXPOSING THE CABLING
<br />AT ANY POINT SHALL BE DEEMED ACCEPTABLE.
<br />78 PROVIDE BACK BOX AND ASSOCIATED CONDUIT, LOCKNUTS, COUPLINGS, THREADED BUSHINGS, AND PULL
<br />ROPE FOR ALL DEVICES AS INDICATED ON DRAWINGS AND AS SPECIFIED.
<br />79 THE FINAL FIELD PLACEMENT AND FIELD OF VIEW FOR EACH CAMERA LOCATION SHALL BE DETERMINED BY ON
<br />SITE CONDITIONS. PRIOR TO THE PURCHASE OF ANY (CCTV) HARDWARE THE CONTRACTOR SHALL OBTAIN
<br />WRITTEN ACCEPTANCE OF PROPOSED PLACEMENTS AND ASSOCIATED FOCAL LENGTHS FROM THE OWNER OR
<br />ITS AUTHORIZED REPRESENTATIVE.
<br />80 ALL PENETRATIONS THROUGH FIRE RATED BUILDING STRUCTURES, WALLS, AND FLOORS SHALL BE SEALED
<br />WITH AN APPROPRIATE FIRE STOP SYSTEM. THIS REQUIREMENT APPLIES TO THROUGH PENETRATIONS
<br />(COMPLETE PENETRATION) AND MEMBRANE PENETRATIONS (THROUGH ONE SIDE OF A HOLLOW FIRE RATED
<br />STRUCTURE). ANY PENETRATING ITEMS I.E., RISER SLOTS AND SLEEVES, CABLES, CONDUIT, CABLE TRAY, AND
<br />RACEWAYS, ETC. SHALL BE PROPERLY FIRE STOPPED. THE CONTRACTOR SHALL ENSURE THAT ANY FIRE STOP
<br />SYSTEMS SHALL BE UL CLASSIFIED TO ASTM E8 14 (UL 1479).
<br />81 THE CONTRACTOR SHALL ENSURE THAT ALL FIRE STOP SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
<br />THE MANUFACTURER'S RECOMMENDATIONS AND SHALL BE COMPLETELY INSTALLED AND AVAILABLE FOR
<br />INSPECTION BY THE LOCAL INSPECTION AUTHORITIES PRIOR TO CABLE SYSTEM ACCEPTANCE.
<br />82 UPON SUCCESSFUL COMPLETION OF THE INSTALLATION, THE CONTRACTOR SHALL CONDUCT FULL SYSTEM
<br />TESTING TO ASSURE THAT THE SYSTEMS ARE CORRECTLY INSTALLED AND FULLY OPERATIONAL. CONFIRM IN
<br />WRITING TO THE ARCHITECT THAT ALL ASPECTS OF THE SYSTEM HAVE BEEN TESTED BY THE CONTRACTOR
<br />AND FOUND TO BE FULLY OPERATIONAL AND READY FOR FINAL ACCEPTANCE TESTING.
<br />83 AT THE CONCLUSION OF TESTING PROVIDE (2) COPIES OF ALL TEST REPORT DOCUMENTATION OF THE TESTS
<br />THAT SHALL REFLECT THE DATE, TIME, AND SYSTEM TESTING RESULTS. ADJUST, BALANCE AND TUNE ALL
<br />EQUIPMENT AS REQUIRED FOR OPTIMUM QUALITY TO MEET MANUFACTURER'S PUBLISHED PERFORMANCE
<br />SPECIFICATIONS AND OWNERS REQUIREMENTS.
<br />1 THE SECURITY MANAGEMENT SYSTEM (SMS) SHALL INTEGRATE THE DIGITAL VIDEO SURVEILLANCE SYSTEM
<br />(DVS), CLIENT WORKSTATIONS, FIELD DATA GATHERING PANELS (FIELD PANELS), CARD READERS, AND EACH
<br />SUPPORT DEVICE AS INDICATED HEREIN AND SPECIFIED IN THE CONTRACT SPECIFICATIONS.
<br />2 ALL WIRING AND CABLE BETWEEN DEVICES SHALL BE IN ACCORDANCE WITH THE OPERATING REQUIREMENTS
<br />OF THE SMS SYSTEM AND SHALL SUPPORT COMMUNICATIONS FOR POINT IDENTIFICATION AND ACCESS
<br />CONTROL TRANSACTIONS TO/FROM EACH DEVICE.
<br />3 THE CONTROL WIRING BETWEEN FIELD DEVICES, REMOTE ACCESS CONTROL EQUIPMENT AND FIELD
<br />PANELS/DATA GATHERING PANELS SHALL BE A MINIMUM OF No. 18 AWG AND SHALL BE COLOR-CODED.
<br />4 PROVIDE WIRING FROM THE SMS FIELD PANEL TO THE INSTALLED FIRE ALARM SYSTEM SUCH THAT IN THE
<br />EVENT OF A FIRE ALARM OR WHEN THE FIRE ALARM SYSTEM IS ACTIVATED, ALL DOORS FITTED WITH
<br />ELECTROMAGNETIC LOCKS SHALL REVERT TO FAIL SAFE MODE OF OPERATION IN ACCORDANCE WITH THE
<br />LOCAL AUTHORITY HAVING JURISDICTION AND OWNER OR THEIR AUTHORIZED REPRESENTATIVE.
<br />5 ALL NON STAIRWELL DOORS FITTED WITH ELECTRIC MORTISE LOCKS SHALL REVERT TO A FAIL SECURE MODE
<br />OF OPERATION IN ACCORDANCE WITH THE LOCAL AUTHORITY HAVING JURISDICTION AND OWNER'S SECURITY.
<br />6 ALL STAIRWELL DOORS FITTED WITH ELECTRIC MORTISE LOCKS SHALL REVERT TO A FAIL SAFE MODE OF
<br />OPERATION.
<br />7 PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20AMP NON-EMERGENCY CIRCUIT THAT IS DEDICATED TO
<br />SECURITY FOR EACH SECURITY EQUIPMENT POWER SUPPLY LOCATION AS INDICATED ON THE DRAWINGS. THE
<br />CIRCUIT CONNECTION SHALL BE PROVIDED WITHIN A BACK BOX, SURFACE MOUNTED AT 18" A.F.F. UNLESS
<br />OTHERWISE NOTED. TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.
<br />8 PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20AMP EMERGENCY CIRCUIT THAT IS DEDICATED TO
<br />SECURITY FOR EACH SECURITY EQUIPMENT POWER SUPPLY LOCATION AS INDICATED ON THE DRAWINGS. THE
<br />CIRCUIT CONNECTION SHALL BE PROVIDED WITHIN A BACK BOX, SURFACE MOUNTED AT 18" A.F.F. UNLESS
<br />OTHERWISE NOTED. TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.
<br />9 PROVIDE AN UNSWITCHED DUPLEX OUTLET CONNECTED TO A 120 VAC, 20AMP EMERGENCY CIRCUIT
<br />DEDICATED TO SECURITY IN THE SECURITY CONTROL CENTER AND EQUIPMENT ROOMS AS INDICATED ON THE
<br />DRAWINGS. THE DUPLEX OUTLET SHALL BE FLUSH MOUNTED WITHIN THE FLOOR BELOW THE CONSOLE
<br />AND/OR EQUIPMENT RACKS. EXACT LOCATION SHALL BE AS DIRECTED BY THE ARCHITECT.
<br />10 PROVIDE A HARD WIRED CONNECTION TO A 120 VAC, 20 AMP NON-EMERGENCY CIRCUIT DEDICATED TO
<br />SECURITY FOR DOORS UTILIZING EXIT DEVICES AS INDICATED ON THE DRAWINGS. THE CIRCUIT CONNECTION
<br />SHALL BE PROVIDED WITHIN A BACK BOX, MOUNTED ABOVE THE CEILING, WITHIN AN ACCESSIBLE LOCATION
<br />ADJACENT TO THE DOOR. TERMINATE WIRE ENDS WITH INSULATED WIRE NUTS.
<br />11 PROVIDE AN UNSWITCHED DUPLEX OUTLET CONNECTED TO A 120 VAC, 20AMP NON-EMERGENCY CIRCUIT
<br />DEDICATED TO SECURITY FOR EACH SECURITY CONVENIENCE DEVICE AS INDICATED ON THE DRAWINGS. THE
<br />OUTLET SHALL BE FLUSH MOUNTED TO THE WALL AT 18" A.F.F UNLESS OTHERWISE NOTED.
<br />12 REVIEW ALL CONTRACT DRAWINGS AND SURVEY EXISTING SITE CONDITIONS PRIOR TO ORDERING EQUIPMENT
<br />OR PROCEEDING WITH WORK.
<br />13 DRAWINGS SHALL BE USED BY THE CONTRACTOR AS A REFERENCE FOR THE REQUIREMENT AND LOCATION OF
<br />THE SYSTEM COMPONENTS. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ACQUAINT
<br />THEMSELVES WITH ALL OF THE CONTRACT DRAWINGS, AND CONFIRM THE REQUIRED QUANTITIES OF DEVICES
<br />AND SPECIFIC OPTIONS ON LOCATION.
<br />14 PERFORM ALL WORK, PROVIDE PRODUCTS, SYSTEM INTEGRATION, COORDINATION, ENGINEERING, AND
<br />DESIGN WORK REQUIRED FOR THE PROJECT IN ORDER TO ENSURE THE PROPER INSTALLATION OF THE
<br />COMPLETE AND FULLY OPERATIONAL SYSTEMS PURSUANT TO THE CONTRACT DOCUMENTS.
<br />15 ALL SYSTEMS PROVIDED SHALL BE IN ACCORDANCE WITH THE MOST CURRENT REVISION OF THE FEDERAL,
<br />STATE, AND LOCAL CODES AND STANDARDS. THE AUTHORITY HAVING JURISDICTION SHALL PROVIDE FINAL
<br />CLARIFICATION OF CODE REQUIREMENTS. CONFLICT OF ANY CODE REQUIREMENT WILL REQUIRE THE
<br />ADAPTATION OF THE MORE STRINGENT REQUIREMENT FOR THE APPLICATION UNLESS A VARIANCE IS
<br />AUTHORIZED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
<br />16 PROVIDE ALL COMPONENTS, INTERCONNECTION CONDUIT, CABLE/WIRE, APPURTENANCES, AND MATERIALS AS
<br />REQUIRE TO FORM A COMPLETE COORDINATED SYSTEM READY FOR OPERATION.
<br />17 PROVIDE ALL PLAN CHECKS, PERMITS, AND LICENSES NECESSARY FOR THE EXECUTION OF WORK AS
<br />APPLICABLE FOR THE PROJECT. ALL FEES, CHANGES, AND OTHER ASSOCIATED COSTS INCURRED BY THE
<br />FOREGOING SHALL BE BORNE BY THE CONTRACTOR.
<br />18 THE CONTRACTOR SHALL PROVIDE A QUALIFIED AND COMPETENT FACTORY TRAINED AND STATE LICENSED
<br />FIELD SUPERVISOR ON-SITE TO ENSURE THE PROPER INSTALLATION OF ALL SYSTEMS SPECIFIED AND IN
<br />ACCORDANCE WITH THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL COORDINATE CONSTRUCTION
<br />ACTIVITIES WITH OTHER CONTRACTORS, TRADES, AND OWNER OR THEIR AUTHORIZED REPRESENTATIVE.
<br />19 THE CONTRACTOR SHALL PROVIDE FACTORY TRAINED AND STATE LICENSED TECHNICIANS FOR THE
<br />INSTALLATION AND SHALL PROVIDE PROOF OF SUCH SYSTEMS AUTHORIZED TRAINING.
<br />20 PROVIDE ALL WIRING FROM EQUIPMENT HARDWARE MANUFACTURER'S TERMINAL STRIPS TO FINAL
<br />CONNECTION POINTS OF EQUIPMENT.
<br />21 THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS AND ANY
<br />CRITICAL DIMENSIONS ASSOCIATED WITH THE SCOPE OF WORK PRIOR TO SUBMITTING THE CONSTRUCTION
<br />BID. THE CONTRACTOR SHALL CONFIRM THAT ALL WORK OUTLINED WITHIN THE CONTRACT DOCUMENTS CAN
<br />BE ACCOMPLISHED AS SHOWN, AND SHALL NOTIFY IN WRITING AN AUTHORIZED REPRESENTATIVE OF ANY
<br />CONDITIONS ENCOUNTERED WHICH MAY AFFECT BUILDING CODE COMPLIANCE.
<br />22 VERIFY PARTITION LOCATIONS, AND AVOID CONFLICTS WITH LIGHTS, DIFFUSERS, GRILLS, AND OTHER LIKE
<br />OBSTRUCTIONS. LOCATIONS OF ALL VISIBLE DEVICES AND EQUIPMENT SHALL BE COORDINATED WITH THE
<br />ARCHITECT FOR REVIEW AND APPROVAL PRIOR TO INITIATION OF WORK.
<br />23 COORDINATE A FINAL SECURITY SYSTEM EQUIPMENT LAYOUT AND ROUTING OF THE CONDUIT WITH THE
<br />CONTRACT DOCUMENTS. ANY CONFLICTS DISCOVERED SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION
<br />OF THE OWNER FOR REVIEW AND APPROVAL PRIOR TO INITIATION OF WORK.
<br />24 EQUIPMENT AND COMPONENTS SHOWN ON THESE PLANS ARE DIAGRAMMATIC IN NATURE AND ARE NOT TO BE
<br />SCALED FOR EXACT DEVICE LOCATIONS. CONTRACTOR SHALL LOCATE DEVICES BASED ON APPLICABLE CODE,
<br />KEY NOTES, AND AS DESIGNED BY THE ARCHITECT.
<br />25 INSTALL ALL MATERIALS AND EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S DIRECTION,
<br />TESTING AND OPERATIONAL PROCEDURES.
<br />26 ALL MATERIALS, DEVICES, AND EQUIPMENT SHALL BE UNUSED, OF CURRENT MANUFACTURER, AND MEET OR
<br />EXCEED THE LATEST PUBLISHED SPECIFICATIONS OF THE MANUFACTURER. DEVICES AND EQUIPMENT SHALL
<br />BE THE LATEST MODEL OF THE MANUFACTURER UNLESS OTHERWISE INDICATED, OR UNLESS SUCH MODEL
<br />FAILS TO MEET THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.
<br />27 ALL ELECTRONICS COMPONENTS SHALL BE STANDARD, UNMODIFIED PRODUCTION MODELS EXCEPT AS NOTED
<br />WITH THE LATEST FIRMWARE/BIOS OFFERED BY THE MANUFACTURER AT THE TIME OF THE FINAL TEST.
<br />28 PROTECT ALL EXISTING WORK, AND THE WORK OF OTHER ASSOCIATED TRADES FROM DAMAGE. ALL
<br />EQUIPMENT PROVIDED SHALL BE KEPT INTERNALLY CLEAN AND PROTECTED AGAINST BLOWING DUST, WIND,
<br />STORMS, SUN, FLOOD, RAIN, SNOW, HEAT, RAIN, MOISTURE, AND ANY OTHER DAMAGING FACTORS. ALL
<br />INSTALLATION WORK SHALL BE COVERED AND PROTECTED AGAINST DAMAGE.
<br />29 EQUIPMENT AND MATERIALS SHALL BE PROPERLY STORED, ADEQUATELY PROTECTED AND CAREFULLY
<br />HANDLED TO PREVENT DAMAGE BEFORE AND DURING INSTALLATION.
<br />30 EQUIPMENT STORED ON THE PREMISES IS AT THE CONTRACTORS OWN RISK. THE OWNER IS NOT THE
<br />CARETAKER OF UNINSTALLED OR STAGING OF HARDWARE ON-SITE UNLESS PREVIOUSLY AUTHORIZED IN
<br />WRITING BY OWNER OR ITS AUTHORIZED REPRESENTATIVE TO ACCEPT CUSTODIANSHIP OF THE HARDWARE.
<br />31 ELECTRICAL CONTRACTOR SHALL PROVIDE PRIMARY, DEDICATED ELECTRICAL POWER (120/220 VAC).
<br />32 ELECTRICAL CONTRACTOR SHALL SUPPLY AND PROVIDE DEDICATED 20 AMP, 120 VAC POWER AT SECURITY
<br />LOCATIONS FOR CONNECTION BY THE SECURITY CONTRACTOR. ALL PRIMARY CONTROL PANELS SHALL BE
<br />CONNECTED TO GENERATOR BACKUP CIRCUITS.
<br />33 ALL PRIMARY CONTROL PANELS, COMMUNICATION TRANSPORTATION DEVICES, POWER SUPPLIES NETWORK
<br />VIDEO RECORDERS, AND DIGITAL VIDEO RECORDERS SHALL BE CONNECTED TO UPS BACKUP CIRCUITS,
<br />BATTERY BACKUP, OR GENERATOR POWER BACKUP SYSTEM.
<br />34 PROVIDE ALL THE INTERCONNECTIONS BETWEEN POWERED JUNCTION BOXES AND THE SECURITY EQUIPMENT.
<br />35 ADHERE TO ALL SYSTEM AND COMPONENT GROUNDING REQUIREMENTS AS SPECIFIED BY THE EQUIPMENT
<br />MANUFACTURERS.
<br />36 PROVIDE SURGE SUPPRESSION, GROUNDING AND BONDING THAT WILL EFFECTIVELY PROTECT, WITHIN
<br />TESTED LIMITS, THE SYSTEMS HARDWARE AND EQUIPMENT AGAINST LIGHTNING TRANSIENTS, INTERNAL AND
<br />EXTERNAL SWITCHING TRANSIENTS, AND OTHER SURGE TRANSIENTS THROUGHOUT THE USEFUL LIFE OF THE
<br />SYSTEM.
<br />37 ALL WIRING SHALL BE PROPERLY SUPPORTED AND INSTALLED IN CONDUIT AND CABLE TRAY, ON CENTER AS
<br />REQUIRED IN CONTRACT DOCUMENTS.
<br />38 ALL CONDUIT FILL SHALL NOT EXCEED 40 PERCENT OF INTERIOR CROSS SECTIONAL AREA WHERE THREE OR
<br />MORE CABLES ARE CONTAINED WITHIN A SINGLE CONDUIT.
<br />39 CABLES, RACEWAYS, AND CONDUIT SHALL NOT BE SUPPORTED FROM DUCTWORK, PIPING, PLUMBING
<br />SYSTEMS, CEILING TILE AND LIGHTING FIXTURE SUSPENSION WIRES OR BUILDING STRUCTURE.
<br />40 CABLES SHALL BE ROUTED IN CONDUIT OR OTHER SUITABLE RACEWAY SUBJECT TO ACCEPTANCE BY THE
<br />ARCHITECT.
<br />41 AT LOCATIONS WHERE CABLES PASS THROUGH METAL STUDS OR DOOR FRAMES, THE CONTRACTOR SHALL
<br />INSTALL A BUSHING OR GROMMET TO PREVENT DAMAGE TO THE CABLES.
<br />42 ALL CABLES MUST BE FREE OF TENSION AT BOTH ENDS AND OVER THE ENTIRE LENGTH OF THE RUN.
<br />43 CABLE TIES AND SUPPORTS SHALL NOT PINCH, BIND, CRIMP, OR IN ANY WAY CAUSE PHYSICAL OR ELECTRICAL
<br />CHARACTERISTIC DAMAGE TO THE CABLING. THE CONTRACTOR SHALL ASSURE THAT DURING AND UPON
<br />COMPLETION OF THE INSTALLATION, ALL CABLES ARE FREE OF KINKS, SHARP BENDS, TWISTS, GOUGES, CUTS
<br />OR ANY OTHER PHYSICAL DAMAGE.
<br />44 ALL CABLING SHALL BE PLENUM RATED IN ACCORDANCE WITH THE NEC.
<br />45 PLENUM RATED CABLE TIES AND CABLE SUPPORTS SHALL BE UTILIZED IN ALL PLENUM RATED SPACES.
<br />46 ALL CABLE RUNS SHALL BE CONTINUOUS BETWEEN DEVICES WITHOUT SPLICES. CONNECTIONS SHALL BE
<br />MADE USING TERMINAL BLOCKS. WIRES CONNECTED TOGETHER SHALL HAVE THE SAME COLOR INSULATION.
<br />ALL CONNECTIONS SHALL BE ACCESSIBLE FOR INSPECTION AND SERVICES AND SHALL BE CLEARLY IDENTIFIED
<br />ON THE CONTRACTOR'S AS-BUILT DRAWINGS. ALL DEVICE BACK BOXES, JUNCTION BOXES AND PULL BOXES
<br />SHALL BE LABELED AND ACCESSIBLE FOR INSPECTION AND MAINTENANCE.
<br />47 WIRING COLOR CODE SHALL BE MAINTAINED THROUGHOUT THE INSTALLATION AS REQUIRED BY THE
<br />SPECIFICATIONS.
<br />NO.ISSUE DATE
<br />PERMIT SET 12.06.2018
|