GENERAL NOTE
<br />CONTRACTOR TO GET ALTERNATE PRICE ON
<br />UPGRADING ENTIRE NURSES CALL SYSTEM.
<br />DW -100 WALL SWITCH/
<br />OCCUPANCY SENSOR DETAL
<br />DT -355 OCCUPANCY SENSOR DETAIL
<br />LOA NEUTRAL
<br />LOAD HOT
<br />SNTCH ® ® NEUTRAL
<br />(OPTIONAL)
<br />GROUND
<br />ELECTRICAL SPECIFICATIONS
<br />PART 1 - GENERAL
<br />A. THE CONTRACTOR SHALL SUPPLY AND INSTALL ALL NEW ELECTRICAL WORK INDICATED.
<br />CONSTRUCTION SHALL BE IN ACCORDANCE WITH DRAWINGS AND APPLICABLE SPECIFICATIONS.
<br />IF A PROBLEM IS ENCOUNTERED IN COMPLYING WITH THIS REQUIREMENT, CONTRACTOR SHALL NOTIFY
<br />THE ARCHITECT /ENGINEER AS SOON AS POSSIBLE AFTER DISCOVERY OF THE PROBLEM AND
<br />SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL ARCHITECT /ENGINEER HAS DIRECTED
<br />CORRECTIVE ACTION TO BE TAKEN.
<br />B. THE CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND FAMILIARIZE HIMSELF WITH ALL
<br />CONDITIONS AFFECTING ELECTRICAL AND COMMUNICATIONS INSTALLATION AND MAKE PROMSIONS AS TO
<br />THE COST THEREOF.
<br />C. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
<br />CODE (AS ADOPTED BY THE AUTHORITY HAMNG JURISDICTION) AND ALL CODES AND ORDINANCES OF THE
<br />AUTHORITY HAVING JURISDICTION. THE SPECIFICATION, CODES AND STANDARDS LISTED BELOW ARE
<br />UTIUZED IN THIS PROJECT.
<br />1. NATIONAL ELECTRICAL CODE (NFPA -70)
<br />2. CODE FOR SAFETY TO LIFE (NFPA -101)
<br />3. STANDARD FOR THE INSTALLATION, MAINTENANCE AND USE OF LOCAL PROTECTIVE SIGNALING
<br />SYSTEMS (NFPA -72)
<br />4. UNDERWRITERS' LABORATORIES (UL)
<br />5. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
<br />6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
<br />7. FEDERAL SPECIFICATION (FED. SPEC.)
<br />S. INSULATED POWER CABLE ENGINEERS ASSOCIATR (IPCEA)
<br />9. FLORIDA BUILDING CODE. 2010 EOMDN (AS AMENDED)
<br />10. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE
<br />11. CITY OF MIAMI BEACH BUILDING CODE (AMENDMENTS TO FL DA BUILDING CODE 2010)
<br />12. ADDITIONALLY, DESIGNS, WORK PRACTICES AND CONDITIONS MUST CONFORM WITH THE
<br />OCCUPATIONAL SAFETY AND HEALTH ACT OF 1970 (OSHA)
<br />D. DO NOT SCALE THE ELECTRICAL DRAWINGS. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS
<br />FOR EXACT LOCATION OF ALL EQUIPMENT. CONFIRM WITH OWNER'S REPRESENTATIVE.
<br />E. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL R CONSTRUCTION. THE
<br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM
<br />AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
<br />F. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FROM A
<br />PERIOD OF NOT LESS THAN RE YEAR FROM DATE OF ACCEPTANCE.
<br />G. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
<br />REPLACEMENT OR REPAIR R ANY OTHER PHASE R THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED
<br />THERE BY.
<br />H. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBUC LIABILITY AND
<br />PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
<br />I. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS AND TESTING. CONTRACTOR
<br />TO OBTAIN PERMIT AND APPROVED SUBMITTALS PRIOR TO BEGINNING WORK OR ORDERING EQUIPMENT.
<br />J. THE TERM "PROVIDE' USED IN THE CONSTRUCTION DOCUMENTS AND SPECIFICATIDNS INDICATES THE
<br />CONTRACTOR SHALL FURNISH AND INSTALL
<br />PART 2 - PRODUCTS
<br />A. MINIMUM WIRE SIZE SHALL BE #12 A.W.C. UNLESS OTHERWISE NOTED,
<br />ALL CONDUCTORS SHALL BE COPPER WITH "THHN -THW4' INSULATION UNLESS OTHERWISE NOTED.
<br />B. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS
<br />IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS.
<br />C. ALL MATERIALS SHALL BE NEW AND BEAR UNDERWRITERS' LABELS WHERE APPLICABLE. CIRCUIT BREAKERS
<br />USED AS SWITCHES IN FLUORESCENT OR HID LIGHTING CIRCUITS SHALL BE LISTED AND MARKED "SWD'.
<br />D. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACR TYPE CIRCUIT BREAKERS.
<br />E. PANELBOARDS AND LOAD CENTERS:
<br />1. CURRENT CARRYING BUSES SHALL BE COPPER. GROUND BUS BARS SHALL BE COPPER.
<br />2. ALL CIRCUIT BREAKERS INSTALLED IN PANELBOARDS SHALL BE BOLT ON.
<br />3. ALL CIRCUIT BREAKERS INSTALLED IN LOAD CENTERS SHALL BE PLUG IN.
<br />4. ALL CIRCUIT BREAKERS FEEDING MECHANICAL EQUIPMENT SHALL BE HACK TYPE CIRCUIT BREAKERS.
<br />5. A.I.C. RATINGS SHALL BE AS INDICATED ON PANELBOARD SCHEDULES.
<br />6. PANELBOARD ENCLOSURES SHALL BE FURNISHED WITHOUT PRE - PUNCHED CONCENTRIC KNOCKOUTS.
<br />7, ALL PANELBOARDS SHALL BE FURNISHED WITH PLASTIC LAMINATE NAMEPLATES WITH 1/4'
<br />ENGRAVED LETTERING FOR PANEL IDENTIFICATION.
<br />EL ALL PANELBOARDS SHALL BE PROVIDED WITH TYPE - WRITTEN DIRECTORY OF BRANCH CIRCUIT
<br />DESIGNATIONS.
<br />F. DISCONNECT SWITCHES SHALL BE H.P. RATED, HEAVY DUTY, QUICK -MAKE, WICK -BREAK ENCLOSURES
<br />AS REWIRED BY EXPOSURE.
<br />G. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED, NTH OVERLOAD RELAYS IN EACH HOT LEG.
<br />H. RIGID NONMETALLIC CONDUIT SHALL BE SCHEDULE 40 PVC.
<br />I. WRING DEVICES (GENERAL PURPOSE RECEPTACLES AND WALL SWITCHES) SHALL BE WHITE COLOR UNLESS
<br />OTHERWISE NOTED. FACEPLATES SHALL BE SMOOTH, WHITE NYLON.
<br />TRANSFER
<br />HOTEL
<br />DEVICE INCLUDES A TEST SWITCH,
<br />SWTCH
<br />^�M
<br />I
<br />NORMAL POWER INDICATOR LIGHT, &
<br />ALTERNATE POWER INDICATOR LIGHT.
<br />EMERGENCY I
<br />POWER -�
<br />N0.
<br />EM
<br />PANEL
<br />GTD20A
<br />BAMAST
<br />TONS
<br />-T
<br />WATTS
<br />WALL
<br />WALL
<br />REMARKS
<br />TYPICAL FLOOR LIGHTING PLANS
<br />Xi )_i 0
<br />NORMAL ..
<br />POWER
<br />I LIGHTING
<br />NORMAL
<br />PANEL
<br />LOAD
<br />VOLTAGE UP TO
<br />ELECTRONIC
<br />SENSING 20A
<br />I
<br />NEUTRAL BUS NEUTRAL BUS
<br />E4.1
<br />FOR NORMAL PANEL FOR EMERGENCY PANEL
<br />F2
<br />BODINE RELAY CONTROL DEVICE
<br />NOT TO SCALE
<br />350OX
<br />J. RECEPTACLES
<br />1. ALL 120 VOLT, SINGLE PHASE, 15 AND 20 AMP BRANCH CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING
<br />UNIT FAMILY ROOMS, DINING ROOMS, UMNG ROOMS, PARLORS, UBRARIES, DENS, BEDROOMS. SUNROOMS,
<br />RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE PROTECTED BY A LISTED
<br />ARC -FAULT CIRCUIT INTERRUPTER, COMBINATION -TYPE, INSTALLED TO PROVIDE PROTECTION OF THE BRANCH
<br />CIRCUIT (NEC 210.12(13)).
<br />2. TAMPER RESISTANT RECEPTACLES (NEC 406.11) ARE REWIRED IN DWEWNG UNITS IN ALL AREAS SPECIFIED IN
<br />2DOB NEC 210.52, ALL 125 VOLT, 15 AND 20 AMP RECEPTACLES
<br />3. 15 AND 20 AMPERE, 125 VOLT AND 250 VOLT RECEPTACLES INSTALLED IN A WET LOCATION SHALL HAVE
<br />AN ENCLOSURE THAT IS WEATHERPROOF WHETHER R NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
<br />15 AND 20 AMPERE, 125 AND 250 VOLT NON- LOCKING RECEPTACLES SHALL BE LIM
<br />WEATHER - RESISTANT TYPE.
<br />PART 3 - EXECUTION
<br />A. COLOR CODING OF CONDUCTORS SHALL BE AS FOLLOWS:
<br />1. 120/208 VOLTS, 3 PHASE, 4 -WIRE SYSTEM: UNGROUNDED CONDUCTORS: 1 BLACK AND 1 RED
<br />GROUNDED (NEUTRAL) CONDUCTOR; WHITE. GROUNDING CONDUCTORS SHALL BE GREEN.
<br />2 PULL CIRCUIT WIRING AND SERVICES
<br />(EXCEPT LB'S OR USD'S) (#6 ING COLOREDS MARKERS OR PLLASTIC TAPE AT ALL
<br />MANUFACTURED FOR THE PURPOSE.
<br />B. WIRING METHODS
<br />1. ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS
<br />OTHERWISE NOTED OR SPECIFICALLY PROHIBITED BY THE AUTHORITY HAVING JURISDICTION. ALL
<br />FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT COMPRESSION TYPE
<br />OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
<br />2. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL
<br />BE INSTALLED UNDERGROUND OR BELOW SLABS R GRADE.
<br />3. ELECTRICAL NONMETALLIC TUBING (EMT) WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE
<br />USE IS ACCEPTABLE FOR USE WITH INTERIOR BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPS OR
<br />LESS AND CONCEALED IN WALLS OR ABOVE SUSPENDED CEILING AND AS APPROVED BY THE
<br />AUTHORITY HAVING JURISDICTION.
<br />4. TYPE MC (METAL CLAD) CABLE WITH ALUMINUM ARMOR AND INTERNAL ROUND IS ACCEPTABLE
<br />FOR USE AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 2D AMPERES OR LESS AND
<br />CONCEALED IN WALLS R ABOVE SUSPENDED CEIUNG AND AS APPROVED BY THE AUTHORITY
<br />HAVING JURISDICTION.
<br />5. TYPE NM (NONMETALLIC SHEATH) CABLE WITH INTERNAL GROUND IS ACCEPTABLE FOR USE
<br />AS GENERAL BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES R LESS AND CONCEALED IN
<br />WALLS OR ABOVE CEILING AND AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.
<br />C. ELECTRICAL SYSTEM SHALL BE COMPLETE AND EFFECTIVELY GROUNDED AS REWIRED BY THE LATEST
<br />EDITION OF THE N.E.C. AND LOCAL CODES.
<br />D. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
<br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY
<br />ENGINEER/ARCHITECT-
<br />E. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS
<br />OF CONSTRUCTION.
<br />F. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF POWER AND TELEPHONE
<br />COMPANIES, AND SHALL BE FULLY COORDINATED WITH THEM PRIOR TO COMMENCEMENT OF WORK.
<br />G. PROVIDE AND INSTALL CONDUIT, CONDUCTORS, PULL WIRES, BOXES, COVER PLATES, AND WIRING
<br />DEVICES, FOR ALL OUTLETS AS INDICATED.
<br />H. MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL COMPONENTS THEREOF, SHALL BE NEW
<br />AND SUCH AS APPEAR R THE UL UST OF APPROVED ITEMS AND SHALL MEET OR EXCEED THE
<br />REQUIREMENTS OF NEC, NEMA, AND IECE.
<br />I. CONTRACTOR SHALL SUBMIT AT LEAST FIVE (5) SETS OF SHOP DRAWINGS OR CUT SHEETS OF LIGHTING
<br />FIXTURES, SWITCHES, AND OTHER ELECTRICAL ITEMS FOR APPROVAL BY ENGINEER /ARCHITECT.
<br />J. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED OF HIS WORK.
<br />K. ALL LAY -IN LIGHTING FIXTURES SHALL BE SECURED TO THE SUSPENDED CEIUNG GRID AT EACH CORNER.
<br />L. CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
<br />WIRING.
<br />M. ALL ELECTRICAL POWER WIRING FOR THE HVAC SYSTEM INCLUDING VARING THRU UNE VOLTAGE CONTROL
<br />DEVICES SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR.
<br />N. VOLTAGE DROP
<br />1. CONDUCTORS FOR ALL FEEDERS SHALL BE INCREASED FROM SIZES INDICATED R RAWNGS TO PREVENT VOLTAGE
<br />DROP EXCEEDING 21L
<br />2. CONDUCTORS FOR ALL BRANCH CIRCUITS SHALL BE INCREASED FROM SIZES INDICATE) R DRAWNGS TO PREVENT
<br />VOLTAGE DROP EXCEEDING 3%. FROM THE FURTHEST DEVICE
<br />3. DETERMINING CONDUCTOR SIZES SHALL BE BASED ON BOX LOAD OF THE BREAKER SIZE.
<br />4. FR DETERMINATION OF WIRE SIZE FOR BID PURPOSES
<br />• INCREASE WRE BY 1 WRE SIZE FOR RUNS 60 FT. TO 1R FT.
<br />• INCREASE WRE BY 2 WRE SIZES FOR RUNS 1DO FT. TO 150 FT.
<br />• INREASE WRE BY 3 WRE SIZES FOR RUNS FROM 150 R. TO 230 FT.
<br />0. PROVIDE CABLE LUGS SIZED FOR THE LINE AND/OR LOAD SIDE FEEDERS AS SCHEDULED FOR ALL SWITCHBOARDS
<br />PANELBOARDS AND DISCONNECTS. WHERE CABLE LUGS ARE NOT AVAILABLE FOR THE SPECIFIC WRE SIZE AND NUMBER OF
<br />SETS SCHEDULED, PROVIDE A TAP BOX ADJACENT TO THE EOUIPMENT WITH 'POLARIS" TAPS TO TRANSITION TO
<br />CONDUCTORS TO MATCH THE CABLE WGS AVAILABLE AND THE AMPERE RATING OF THE OVER- CURRENT DEME
<br />PROTECTING THE FEEDER.
<br />P. THE CONTRACTOR SHALL CONFIRM WITH THE ELECTRICAL UTILITY COMPANY ANY AND ALL REQUIREMENTS
<br />SUCH AS: METERING EQUIPMENT REQUIREMENTS AND METERING EQUIPMENT LOCATION, TRANSFORMER
<br />SIZE AND LOCATION OR SERVICE POINT, CONDUIT ENTRY AND LUG SIZE RESTRICTIONS.
<br />0. THE CONTRACTOR SHALL SCHEDULE ALL REQUIRED DOWN TIME FOR THE OWNERS CONFIRMATION.
<br />R. ANY CONFLICTS AND DESCREPANCIES SHALL BE BROUGHT TO THE ATTENTION R THE ENGINEER BEFORE
<br />PROCEEDING WITH ANY WORK.
<br />LIGHTING FIXTURE SCHEDULE
<br />BFffT•
<br />MML
<br />TYPE
<br />DESDOPTION
<br />N0.
<br />LAMPS
<br />TYPE
<br />WATT
<br />BAMAST
<br />TONS
<br />-T
<br />WATTS
<br />MOUNTING
<br />REMARKS
<br />TYPICAL FLOOR LIGHTING PLANS
<br />F7
<br />7v1' FLUORESfINf dRECTANgRECi RXNRE, WWAY6 'd' SERFS
<br />J
<br />&IOUX
<br />28
<br />ELECTRONIC
<br />E3.3
<br />RECESSED
<br />E4.1
<br />❑
<br />F2
<br />2' #' RUdSSCVTf gRFCT/INgRECT R %LURE, WLlAYS 'd' SERFS
<br />2
<br />350OX
<br />11
<br />EIFC1R01I C
<br />RECESSED
<br />RUORESCENT OPEN REFLECTOR DOWN UG 07H C APERTURE, GEAR TRIM AND SPECUAR
<br />1
<br />GL
<br />32
<br />EIECIRRIC
<br />J!
<br />CORG
<br />0
<br />F3
<br />LOW HDESCENT FIMS. IWNITY'KW SERIES
<br />3500%
<br />RECESSED
<br />O
<br />F4
<br />PENDANT MOUNTED CHANDELIER SEEM BY ARCHIECT
<br />-
<br />_
<br />_
<br />_
<br />IM
<br />COMING
<br />PDDANT
<br />RUMMUT MAW -IXM CHANNEL M1 MIME SAKE) ENAMOR HNIS4 AND
<br />2
<br />TB
<br />32
<br />HIGH FRED.
<br />57
<br />COUNG
<br />�-1
<br />F5
<br />SfALYAD -R DD PLATES WWN1S '76' SERIES
<br />35M
<br />OECTROMC
<br />SIffACE
<br />SNO E FAM 1MRMOPLASDC EDT 9GNAIGHT WITH MIR HOUSING AND RED LETTERS
<br />-
<br />®
<br />X1
<br />PRGYDE ORE00NAL ARROWS AS INWARD, BECHM 'VA4RSA' SFA OS ES PROM FIXTURE FIXTURE
<br />-
<br />�
<br />-
<br />-
<br />UNIVERSAL
<br />W1H 1N MINUTE BATTERY BACK UP.
<br />DUAL FACE THERMRUSRC DOT SGNAIGHT WITH WILE HOUSING AND RED LETTERS
<br />%2
<br />PROWS NUCTIORAL ARROWS AS INDICATED. MOW 'VA4RSA' SERIES. PROMS ROURE
<br />LED
<br />-
<br />UNNERSAL
<br />07H Po CUNT: BATTERY BACK UP.
<br />+2..
<br />12
<br />25
<br />-
<br />GENERAL NOTES 3. PROVIDE ALL FLUORESCENT FIXTURES THAT UTILIZE DOUBLE -ENDED LAMPS AND
<br />CONTAIN BALLASTS WTH A BUILT -IN MEANS TO DISCONNECT THE BALLAST FROM
<br />1. VERIFY CEILING TYPES PRIOR TO ORDERING FIXTURES THE SIRE E SUPPLY.
<br />2 TEMPORARY URTING
<br />4. VERIFY BALLAST REQUIREMENTS FOR ALL FLUORESCENT FIXTURES. PROLE
<br />ELECTRONIC DIMMING BALLASTS FOR SPECIFIC FIXTU RES INDICATED WITH DIMMER
<br />CONTROL
<br />ELECTRICAL SHEET INDEX
<br />BFffT•
<br />DESCRIPTION
<br />E0.1
<br />ELECTRICAL NOTES, LEGEND & INDEX
<br />t
<br />DNNHieIU Dc h FlunJa 33442
<br />Phone 934.949.2200 Pss 954.949 2201
<br />E1.2
<br />SITE PHOTOMETRICS PLAN
<br />E2.1
<br />GROUND FLOOR LIGHTING PLANS
<br />E2.2
<br />TYPICAL FLOOR LIGHTING PLANS
<br />E3.1
<br />GROUND FLOOR POWER PLANS
<br />E3.1A
<br />KITCHEN EQUIPMENT POWER PLAN
<br />E3.2
<br />TYPICAL FLOOR POWER PLANS
<br />E3.3
<br />ELECTRICAL ROOF PLAN
<br />E4.1
<br />TYPICAL APARTMENT ELECTRICAL PLANS
<br />E5.1
<br />ELECTRICAL RISER DIAGRAM
<br />E6.1
<br />ELECTRICAL PANELBOARD SCHEDULES
<br />E6.2
<br />ELECTRICAL PANELBOARD SCHEDULES
<br />ELECTRICAL SYMBOLS
<br />TELEPHONE/DATA OUTLET WITH 3/4" CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.
<br />0 MOUNT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS OTHERWISE NOTED.
<br />TELEVISION OUTLET PATH 3/4' CONDUIT STUBBED OUT FROM WALL 6" ABOVE CEILING.
<br />MOUNT AT 18" A.F.F. TO CENTER LINE R OUTLET UNLESS OTHERWISE NOTED.
<br />(ID DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) MOUNTED AT
<br />7I 18" A.F.F. TO CENTER LINE R OUTLET UNLESS NOTED OTHERWISE.
<br />QUADRUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING)
<br />MOUNTED AT 18" A.F.F. TO CENTER LINE OF OUTLET UNLESS NOTED OTHERWISE.
<br />QGFI DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) WITH GROUND
<br />FAULT CIRCUIT INTERRUPTER, MOUNT AT 18" A.F.F. TO CENTER LINE OF OUTLET. UNLESS
<br />NOTED OTHERWISE.
<br />qp DUPLEX RECEPTACLE (AMPERAGE RATING TO MATCH BRANCH CIRCUIT RATING) MOUNTED
<br />if ABOVE COUNTER SEE ARCHITECTUAL DRAWINGS FOR SPECIFIC REQUIREMENTS.
<br />I$ SPECIAL- PURPOSE RECEPTACLE
<br />Q JUNCTION BOX
<br />EF EXHAUST FAN. SEE MECHANICAL DRAWINGS FOR SPECIFICATIONS.
<br />$ SINGLE POLE, 20 AMP, SWATCH. MOUNT 42" A.F.F. TO CENTERLINE OF SWITCH UNLESS
<br />OTHERWISE NOTED.
<br />$M MOTOR RATED SWITCH
<br />$1G DUAL TECHNOLOGY WALL SWITCH /OCCUPANCY SENSOR, WATT STOPPER DW -100 SERIES.
<br />MOUNT 42' A.F.F. TO ENTERUNE OF SWTCH UNLESS OTHERWISE NOTED. SEE DETAIL R SHEET EO.1
<br />30 MINUTE MAXIMUM TIME DELAY.
<br />OS 120/277 VAC DUAL TECHNOLOGY OCCUPANCY SENSOR, WATT STOPPER DT -355 SERIES.
<br />MOUNT IN COILING. SEE DETAIL ON THIS SHEET. 30 MINUTE MAXIMUM TIME DELAY.
<br />® FACTORY MOUNTED DISCONNECT /STARTER (SEE MECHANICAL SCHEDULE)
<br />d gA FUSIBLE DISCONNECT SWITCH A = POLES, B= FRAME SIZE. G FUSE RATING
<br />tM BA FUSIBLE DISCONNECT SWITCH TYPE COMBINATION MOTOR STARTER A = POLES. B= NEMA SIZE,
<br />C= FUSE RATING
<br />1 GROUNDING ELECTRODE & CONDUCTOR SYSTEM
<br />® TRANSFORMER
<br />0 ELECTRICAL PANELBOARD
<br />r,-- TELEPHONE WOOD BACKBOARD
<br />WP WEATHERPROOF
<br />T/C TIME CLOCK
<br />RE RELOCATED
<br />E EXISTING TO REMAIN
<br />A.F.F. ABOVE FINISH FLOOR
<br />,7/' GALLO HERBERTARCHITECTS
<br />J- a\2e0o1Ta1
<br />1311 W NEWPORT CENTER DRIVE
<br />DEERFIELD BEACH, FLORIDA 33442
<br />PH. 954.784.0300 FX. 954.794.0301
<br />AA-0002853
<br />SEAL
<br />GHLLO FL 4
<br />R0
<br />c 1.
<br />3 0
<br />2
<br />a
<br />PbH >i LB30'j0V
<br />_ . SULTANTS
<br />IssTIRD FUx e6xAm
<br />15311EU FOR CONSTRUCTION
<br />NMMI WN6ULTNO PRO16CI p N410
<br />PROIECI RLANAGFX WIBRWY.\
<br />1407 West Newport Ccnter Dniv
<br />MIKAM
<br />DNNHieIU Dc h FlunJa 33442
<br />Phone 934.949.2200 Pss 954.949 2201
<br />Oh T>0
<br />Ce tilicntion 1'Aullwrizolion8k8189
<br />,e4
<br />MARIAN TOWERS
<br />SITE PLAN APPROVAL
<br />17505 NORTH BAY RD
<br />SUNNY ISLES BEACH. FL 33160
<br />PROJECT NUMBER -
<br />43 -2013
<br />AS NOTED
<br />DRRNNBY CHEC DW
<br />MU BH
<br />-.-No TRLE
<br />ELECTRICAL NOTES
<br />DMWINGNUMBER
<br />E0.1 7]