Lighting Controls Plan & DetailsE104UNSWITCHED LIGHTING POWER CIRCUITROOMCTRLLIGHTOSOSTYPICAL CEILING MOUNTED LOW VOLTAGE OCCUPANCYSENSOR(S). WHERE MULTIPLE SENSORS ARE INDICATED IN ASINGLE CONTROL ZONE, ALL LIGHTS SHALL BE CONTROLLEDAS A SINGLE ZONE BASED ON DETECTION BY ANY SINGLESENSOR, UON.TO REMAINING LIGHTFIXTURES IN CONTROL ZONESWITCHED AND 0-10V CONTROLLIGHTING CIRCUITTYPICAL LIGHT FIXTURE WITH 0-10VDIMMING CONTROL, REFER TOLIGHTING FIXTURE SCHEDULE.LOW VOLTAGE LIGHTING CONTROL CIRCUITBASIS OF DESIGN: HUBBELL NXRC ROOM CONTROLLER. PROVIDE SINGLEOR DUAL RELAY AS REQUIRED PER FLOOR PLAN CONTROL DESIGINATIONS.PROVIDE ADDITIONAL ROOM CONTROLLERS AS REQUIRED AND NETWORKPER MFRS INSTALLATION INSTRUCTIONS.DIGITAL WALL SWITCHES. REFER TO FLOOR PLAN FORAND DIGITAL SWITCH SCHEDULE FOR FURTHER DETAILS.LOW VOLTAGE CONTROL CIRCUIT TOWALL SWITCHES1.2.3.NOTES:AUTO ON: 50% OUTPUTAUTO OFF: AFTER 30 MIN - NO OCCUPANCYDIGITAL SWITCH(ES): REFER TO SCHEDULEFOR OPERATIONLIGHTTO REMAINING LIGHT FIXTURES INCONTROL ZONETYPICAL LIGHT FIXTUREWALL MOUNTED DUAL-TECH OCCUPANCY SENSORSWITCHUNSWITCHED LIGHTING POWER CIRCUIT1.2.3.NOTES:AUTO ON: 50% OUTPUTAUTO OFF: AFTER 30 MIN - NO OCCUPANCYPUSH BUTTON: ON @ 100%, OFFSWITCHED LIGHTING CIRCUITLIGHTTO REMAINING LIGHT FIXTURES INCONTROL ZONETYPICAL LIGHT FIXTUREWALL MOUNTED DUAL-TECH OCCUPANCY SENSORSWITCH WITH 0-10V DIMMING CONTROL ANDMANUAL ON/OFF PUSH BUTTON.UNSWITCHED LIGHTING POWER CIRCUIT1.2.3.NOTES:AUTO ON: 50% OUTPUTAUTO OFF: AFTER 30 MIN - NO OCCUPANCYPUSH BUTTON: ON @ 100%, OFFSWITCHED AND 0-10V CONTROLLIGHTING CIRCUITS1.2.3.NOTES:THE ABOVE DETAIL IS SCALABLE FOR NUMBER OF CONTROL ZONESAS INDICATED ON THE FLOOR PLAN. CONTRACTOR SHALL APPLY THEDESIGN INTENT INDICATED ABOVE AS APPLICABLE. PROVIDE ALLCOMPONENTS AS REQUIRED TO MATCH THE DESIGN INTENT.CONTROL ZONES MAY INCLUDE 0-10V DIMMING VIA PROGRAMMING,DIGITAL SWITCH OR DAYLIGHT SENSOR CONTROL. WHEREAPPLICABLE, PROVIDE 'EM' FIXTURES WITH 0-10V DIMMING.CONTRACTOR TO PROVIDE CONTROL WIRING FROM LCP TO FIXTURESAS REQUIRED. REFER TO LCP/ELCP SCHEDULES FOR DIMMINGDETAILS BY ZONE.PROVIDE CAT 5E NETWORK TO ALL DIGITAL SWITCHES, OCCUPANCYSENSORS, AND DAYLIGHT SENSORS AND TERMINATE ATLCP-1/ELCP-1. NO SWITCHES OR DEVICE CAPABLE OF BREAKINGCIRCUIT SHALL BE INSTALLED ON THE LOAD SIDE OF LIGHTINGCONTROL PANELS.NORMAL POWERPANELLCP-1RXRYDAYLIGHTSENSOROCCUPANCYSENSOR INPUTDIGITAL SWITCHINPUTOSPREFER TO FLOOR PLANS FOR OCCUPANCY SENSOR DESIGNATION.ANY (1) OCCUPANCY SENSOR WITHIN THE ZONE SHALL TURN ON ALLFIXTURES WITHIN THE ZONE.PHOTOCELL TO BE MOUNTED ON ROOF. COORDINATE FINALLOCATION IN THE FIELD. PROVIDE CONDUIT STUB-UP / PIPE BOOTAND WIRING BACK TO LCP-1, AS INDICATED.LIGHTRXLIGHTRY0-10V CONTROLMANUAL OVERRIDE SWITCH AS APPLICABLELC#1LC#2LC#3LC#4http://www.beai.com <br />PHONE: (305) 461-2053 <br />LICENSE No. AA26001612 <br />Miami, Florida 33168 <br />11575 Northwest 7 Avenue <br />FAX: (305) 634-0599 <br />E-mail: info@beai.com <br />BEA architects Inc. <br />© a r c h i t e c t sNOVEMBER 25, 2024CITY OF SUNNY ISLES BEACH <br />18050 COLLINS AVENUE, SUNNY ISLES BEACH, FLORIDA 3316021-1011PERMIT SETBUILDING DEPARTMENT RELOCATION <br />TO ANNEX <br />THIS ITEM HAS BEEN DIGITALLY SIGNED AND <br />SEALED BY ALEX ROBINSON ON THE DATE <br />ADJACENT TO THE SEAL. PRINTED COPIES OF <br />THIS DOCUMENT ARE NOT CONSIDERED SIGNED <br />AND SEALED AND THE SIGNATURE MUST BE <br />VERIFIED ON ANY ELECTRONIC COPIES.www.hammondengineers.com499 N.W. 70thAvenue,Suite 215Plantation, Florida 33317