My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
2019-01-09_GATEWAY PARK CENTER_CONFORMED DRAWINGS FOR BID
SIBFL
>
City Clerk
>
Bids-RFQ-RFP
>
ITB
>
(19-01-01) Gateway Park Center
>
2019-01-09_GATEWAY PARK CENTER_CONFORMED DRAWINGS FOR BID
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
1/31/2019 11:43:53 AM
Creation date
1/31/2019 11:23:07 AM
Metadata
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
139
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
NOTE: <br />ALL WALL MOUNTED FACEPLATES SHALL BE MOUNTED ONTO A 4-11/16"x4-11/16"x3" DOUBLE GANG BACK BOX. EACH DOUBLE GANG BACK BOX SHALL <br />BE FITTED WITH A SINGLE OR DOUBLE GANG PLASTER RING TO ACCEPT SINGLE OR DOUBLE GANG FACEPLATES RESPECTIVELY. INSTALL A 1-1/4" <br />CONDUIT FROM BACK BOX TO WITHIN 6" OF THE CABLE SUPPORT SYSTEM. PROVIDE PULL STRING WITHIN ALL TELECOMMUNICATIONS CONDUITS. <br />1.INSTALL CONDUIT RUNS IN THE MOST DIRECT ROUTE POSSIBLE WITH NO MORE THAN TWO 90 DEGREE BENDS BETWEEN PULL POINTS OR PULL <br />BOXES. <br />2.90 DEGREE CONDUITS "LB" TYPE FITTINGS SHALL NOT BE USED FOR TELECOMMUNICATIONS CABLING INSTALLATIONS. <br />3.CONTINUOUS CONDUIT SECTIONS OR SEGMENTS SHALL NOT BE GREATER THAN 100 LINEAR FEET IN LENGTH WITHOUT AN ADEQUATELY SIZED <br />PULL BOX -REFER TO DETAIL <br />4.CONDUITS SHALL BE BONDED TO GROUND ON ONE OR BOTH ENDS IN ACCORDANCE WITH NATIONAL AND LOCAL REQUIREMENTS. <br />5.TELECOMMUNICATIONS CONDUITS SHALL BE INSTALLED TO WITHSTAND THE ENVIRONMENT IN WHICH THEY WILL BE EXPOSED AND IN <br />ACCORDANCE WITH ANSI/NFPA-70; THE NATIONAL ELECTRICAL CODE. <br />6.THE TOTAL DISTANCE OF CONDUIT RUNS FOR TELECOMMUNICATIONS HORIZONTAL CABLE USE SHALL NOT EXCEED 150 FEET. <br />7.DO NOT INSTALL CONDUITS OVER OR ADJACENT TO BOILERS, INCINERATORS, HOT WATER OR STEAM LINES. <br />8.THE MINIMUM BEND RADIUS OF ANY PORTION OF THE CONDUIT PATHWAY SHALL BE SIX (6) TIMES THE INTERNAL DIAMETER OF THE CONDUIT <br />FOR ALL CONDUITS 2-INCHES IN DIAMETER OR LESS. <br />9.THE MINIMUM BEND RADIUS OF ANY PORTION OF THE CONDUIT PATHWAY SHALL BE TEN (10) TIMES THE INTERNAL DIAMETER OF THE CONDUIT <br />FOR ALL CONDUITS WITH AN INTERNAL DIAMETER GREATER THAN 2-INCHES. <br />10.WHERE A CONDUIT RUN REQUIRES A REVERSE BEND (BETWEEN 100 DEGREES AND 180 DEGREES) A PULL BOX SHALL BE INSTALLED AT EACH <br />BEND HAVING SUCH ANGLE, WITHIN 10 FEET OF THE BEND. <br />11.IF A CONDUIT RUN REQUIRES A THIRD 90 DEGREE BEND BETWEEN PULL POINTS OR PULL BOX, THE OVERALL DESIGN CAPACITY OF THE CONDUIT <br />SYSTEM SHALL HAVE A DERATED TOTAL CAPACITY OF 15 PERCENT. <br />12.ALL CONDUIT ENDS SHALL BE REAMED AND FITTED WITH THREADED INSULATING BUSHING TO ELIMINATE SHARP EDGES THAT CAN DAMAGE <br />CABLES DURING INSTALLATION. <br />13.CONDUITS THAT PROTRUDE THROUGH WALLS AND FLOORS SHALL BE EXTENDED BEYOND THE SURFACE PENETRATION TO WITHIN 12 INCHES <br />OF THE CABLE TRAY OR CABLE RUNWAY SYSTEM. <br />14.ALL TELECOMMUNICATION OUTLETS STUB-UPS SHALL BE EQUIPPED WITH A PULL STRING WITH A MINIMUM TEST RATING OF 200 LBS. <br />15.ALL INTERIOR COMMUNICATIONS CONDUITS GREATER THAN 1 1/2" CONDUITS SHALL BE EQUIPPED WITH 1/2" CABLE PULL STRING WITH 1250 LBS <br />OF TENSILE STRENGTH AND SEQUENTIAL FOOTAGE MARKING. <br />16.ALL EXTERIOR COMMUNICATIONS CONDUITS SHALL BE EQUIPPED WITH 1/2" CABLE PULL STRING WITH 1250 LBS OF TENSILE STRENGTH AND <br />SEQUENTIAL FOOTAGE MARKING. <br />17.INSTALL PULL BOXES IN ACCESSIBLE LOCATIONS. DIRECT ACCESS TO PULL BOXES IS REQUIRED. PROVIDE LABELED, HINGED ACCESS PANEL <br />DOOR. PULL BOXES SHALL BE LISTED FOR THE PURPOSE. <br />18.THE MINIMUM LENGTH OF PULL BOX SHALL BE 12 TIMES THE DIAMETER OF THE LARGEST CONDUIT. PULL BOXES SHALL NOT BE USED IN <br />SUBSTITUTION OF A 90 DEGREE BEND. <br />19.REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING ELEVATIONS. <br />20.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR COORDINATION OF ALL CONDUIT, RUNWAY, AND TRAY. <br />21.COORDINATE EXACT LOCATIONS OF ALL FLOOR BOXES AND POKE-THRU DEVICES WITH ARCHITECT PRIOR TO INSTALLATION. <br />22.ALL OUTLET LOCATIONS AND DIMENSIONS ARE APPROXIMATE. COORDINATE EXACT MOUNTING LOCATION AND HEIGHT WITH ARCHITECTURAL <br />DRAWINGS PRIOR TO INSTALLATION. <br />23.WHERE CABLE TRAY RUNS ARE OBSTRUCTED, J-HOOKS MAY BE USED. J-HOOKS SHALL BE SPACED NO LESS THAN 48" O.C AND NOT GREATER <br />THAN 60" O.C. WHERE COMMUNICATIONS CABLE AND SECURITY CABLE FOLLOW THE SAME PATH, CABLES SHALL BE SEPARATED. ALL <br />TELECOMMUNICATION OUTLETS SHOWN IN OPEN AIR ENVIRONMENT (I.E. MECHANICAL SPACE, PENTHOUSE, ROOF, GARAGE) SHALL BE <br />INSTALLED IN CONDUIT, RATED FOR THAT ENVIRONMENT. <br />24.ALL TELECOMMUNICATIONS HORIZONTAL STRUCTURED CABLING SHALL BE INSTALLED IN MAIN AND SECONDARY CORRIDORS ONLY FROM <br />TELECOMMUNICATIONS ROOM TO WORK AREA OUTLETS. <br />25.ALL TELECOMMUNICATIONS HORIZONTAL STRUCTURED CABLING SHALL ENTER WORK AREA ROOMS VIA PROPERLY SIZED CONDUIT ABOVE <br />DOOR. CONDUIT SLEEVE SHALL BE PROPERLY FIRESTOPPED TO MAINTAIN FIRE RATING. <br />26.UNDER NO CIRCUMSTANCES SHALL TELECOMMUNICATIONS HORIZONTAL STRUCTURED CABLING BE INSTALLED THROUGH ADJACENT ROOMS <br />TO WORK AREA OUTLETS. <br />4 <br />1 <br />COMMUNICATIONS LEGEND <br />GENERAL PATHWAY REQUIREMENTS <br />POI POINT OF INTERFACE <br />POTS PLAIN OLD TELEPHONE SERVICE <br />PR PAIR <br />PTSS PASSIVE TRANSMISSION SUBSYSTEM <br />PVC POLYVINYL CHLORIDE <br />SE SERVICE ENTRANCE <br />SER SATELLITE EQUIPMENT ROOM <br />SI SYSTEM INTERNATIONAL <br />SL SLEEVE <br />SMPS SWITCHED MODE POWER SUPPLY <br />SNA SYSTEMS NETWORK ARCHITECTURE <br />SP SERVICE PROVIDER <br />SPC STORED PROGRAM CONTROL <br />SPD SURGE PROTECTION DEVICE <br />SPG SINGLE-POINT GROUND <br />STA STATION <br />STP SHIELDED TWISTED PAIR <br />SW STATION WIRE <br />SWB SWITCHBOARD <br />SYS SYSTEM <br />TB TERMINAL BLOCK <br />TBBC TELECOMMUNICATIONS BACKBONE BONDING CONDUCTOR <br />TBC TELECOMMUNICATION BONDING CONDUCTOR <br />TC TELECOMMUNICATIONS CLOSET <br />TDM TIME DIVISION MULTIPLEXING <br />TEBC TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR <br />TEL TELEPHONE <br />TELCO TELEPHONE COMPANY <br />TERM TERMINAL <br />TGB TELECOMMUNICATIONS GROUNDING BUSBAR <br />THD TOTAL HARMONIC DISTORTION <br />TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION <br />TM TRANSFORMER MAINTENANCE HOLE <br />TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR <br />TO TELECOMMUNICATIONS OUTLET <br />TPDDI TWISTED PAIR DISTRIBUTED DATA INTERFACE <br />TPPMD TWISTED PAIR PHYSICAL MEDIUA DEPENDENT <br />TR TELECOMMUNICATIONS ROOM <br />TSB TELECOMMUNICATIONS SYSTEM BULLETIN <br />TT TELEPHONE TERMINAL <br />TTB TELEPHONE TERMINAL BOARD <br />TTY TEXT TELEPHONES <br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR <br />TYP TYPICAL <br />UG UNDERGROUND <br />UL UNDERWRITERS LABORATORIES <br />UPS UNINTERRUPTIBLE POWER SUPPLY <br />UTP UNSHIELDED TWISTED PAIR <br />ISDN INTEGRATED SERVICES DIGITAL NETWORK <br />ISO INTEGRATED STANDARDS ORGANIZARION <br />IW INSIDE WIRING (CABLE) <br />KHz KILOHERTZ <br />KTS KEY TELEPHONE SYSTEM <br />LAN LOCAL AREA NETWORK <br />LASER LIGHT AMPLIFICATION BY STIMULATED EMISSION OF RADIATION <br />LATA LOCAL ACCESS TRANSPORT AREA <br />LBO LINE BUILDOUT <br />LEC LOCAL EXCHANGE CARRIER <br />LED LIGHT EMITTING DIODE <br />LOCAP LOW CAPACITANCE <br />MAP MANUFACTURING AUTOMATION/PROTOCOL <br />MAX MAXIMUM <br />MC MAIN CROSS-CONNECT <br />MDF MAIN DISTRIBUTION FRAME <br />M/G MOTOR/GENERATOR SET <br />MH MAINTENANCE HOLE <br />MICRON MICROMETER <br />MIN MINIMUM <br />MISC MISCELLANEOUS <br />MODEM MODULATOR/DEMODULATOR <br />MPOP MINIMUM POINT OF PRESENCE <br />MTT MAIN TELEPHONE TERMINAL <br />N NEWTON <br />NEC NATIONAL ELECTRIC CODE <br />NESC NATIONAL ELECTRIC SAFETY CODE <br />NI NETWORK INTERFACE <br />NIC NOT IN CONTRACT <br />NID NETWORK INTERFACE DEVICE <br />NIU NETWORK INTERFACE UNIT <br />NRTL NATIONALLY RECOGNIZED TESTING LABORATORY <br />NTS NOT TO SCALE <br />OC ON CENTER <br />OD OUTSIDE DIAMETER <br />OFNP OPTICAL FIBER NON-CONDUCTIVE PLENUM <br />OFNR OPTICAL FIBER NON-CONDUCTIVE RISER <br />OPD OVERCURRENT PROTECTION DEVICE <br />OPE OUTSIDE PLANT ENGINEER <br />OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION <br />OSP OUTSIDE PLANT <br />PAM PULSE AMPLITUDE MODULATE <br />PB PULL BOX <br />PBX PRIVATE BRANCH EXCHANGE <br />PCM PULSE CODE MODULATION <br />PIC POLYETHYLENE INSULATED CONDUCTOR <br />PL PRIVATE LINES <br />PLT PLANT <br />PM PHASE MODULATION <br />D/A DIGITAL TO ANALOG CONVERSION <br />DAF DEDICATED ACCESS FACILITY <br />DB DECIBEL <br />DC DIRECTED CURRENT <br />DCE DATA CIRCUIT-TERMINATION EQUIPMENT <br />DCO DIGITAL CENTRAL OFFICE <br />DD DISTRIBUTION DESIGNER <br />DEMARC DEMARCATION POINT <br />DGM DATA GRADE MEDIUM <br />DTE DATA TERMINAL EQUIPMENT <br />DW DISTRIBUTION WIRE <br />DWG DRAWING(S) <br />EBC EQUIPMENT BONDING CONDUCTOR <br />EC ELECTRICAL CONTRACTOR <br />EF ENTRANCE FACILITY <br />EIA ELECTRONICS INDUSTRY ASSOCIATION <br />ELEC ELECTRICAL <br />EMC ELECTROMAGNETIC COMPATABILITY <br />EMI ELECTROMAGNETIC INTERFACE <br />EMR ELECTROMAGNETIC RADIATION <br />EMT ELECTRICAL METALLIC TUBING <br />ESS ELECTRONIC SWITCHING SYSTEM <br />ETV EDUCATIONAL TELEVISION <br />E/W EQUIPPED WITH <br />EXCH EXCHANGE <br />EXT EXTENSION <br />FCC FEDERAL COMMUNICATIONS COMMISSION <br />FD FLOOR DISTRIBUTION <br />FDDI FIBER DISTRIBUTION DATA INTERFACE <br />FDM FREQUENCY DIVISION MULTIPLEXING <br />FDR FEEDER <br />FO FIBER OPTIC <br />FOTP FIBER OPTIC TRANSMISSION SYSTEM <br />FREQ FREQUENCY <br />FTP FOIL TWISTED PAIR <br />GA GAUGE <br />GEC GROUNDING ELECTRIC CONDUCTOR <br />GHz GIGAHERTZ <br />GND GROUND <br />HC HORIZONTAL CROSS-CONNECT <br />HF HIGH FREQUENCY <br />HH HANDHOLE <br />HVAC HEATING, VENTILATION AND AIR CONDITIONING <br />Hz HERTZ <br />IC INTERMEDIATE CROSS-CONNECT <br />ICEA INSULATED CABLE ENGINEERS ASSOCIATION <br />IDC INSULATION DISPLACEMENT CONNECTION <br />IDF INTERMEDIATE DISTRIBUTION FRAME <br />IEEE INTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS <br />8P8C 8-POSITION, 8-CONDUCTOR <br />AC ALTERNATING CURRENT <br />A/D ANALOG TO DIGITAL CONVERSION <br />ACO ANALOG CENTRAL OFFICE <br />ADA AMERICANS WITH DISABILITIES ACT <br />ADO AUXILIARY DISCONNECT OUTLET <br />AER AERIAL <br />AFF ABOVE FINISHED FLOOR <br />AIA AMERICAN INSTITUTE OF ARCHITECTS <br />AM AMPLITUDE MODULATION <br />ANSI AMERICAN NATIONAL STANDARDS INSTITUTE <br />ARMM PIC RISER, EXPANDED POLYETHYLENE PVC, 24 AWG, ALVYN <br />ASCII AMERICAN STANDARD CODE FOR INFORMATION INTERCHANGE <br />ATM ASYNCHRONOUS TRANSFER MODE <br />AWG AMERICAN WIRE GAUGE <br />B BURIED <br />BC BONDING CONDUCTOR <br />BBISDN BROADBAND INTEGRATED SERVICES DIGITAL NETWORK <br />BD BUILDING DISTRIBUTOR <br />BDF BUILDING DISTRIBUTION FRAME <br />BEF BUILDING ENTRANCE FACILITY <br />BER BIT ERROR RATE <br />BIC BUILDING INDUSTRY CONSULTANT <br />BICSI BUILDING INDUSTRY CONSULTING SERVICES <br />BRISDN BASIC RATE INTEGRATED SERVICES DIGITAL NETWORK <br />BTU BRITISH THERMAL UNIT <br />CA CABLE <br />CATV CABLE TELEVISION <br />CBC COUPLED BONDING CONDUCTOR <br />CC COMMUNICATIONS CONTRACTOR <br />CCITT THE INTERNATIONAL TELEGRAPH AND TELEPHONE CONSULTATIVE COMMITTEE <br />CD CONDUIT <br />CDDI COPPER DISTRIBUTED DATA INTERFACE <br />CDF COPPER DISTRIBUTION FRAME <br />CDO COMMUNITY DIAL OFFICE <br />CER COMPUTER EQUIPMENT ROOM <br />CIRC CIRCUIT <br />CFC COMMUNICATIONS FLAT CABLE <br />CLO CLOSET <br />CO CENTRAL OFFICE <br />CODEC CODER/DECODER <br />COE CENTRAL OFFICE EQUIPMENT <br />COT CENTRAL OFFICE TERMINAL <br />CPC CUSTOMER PREMISES COMMUNICATIONS <br />CPE CUSTOMER PREMISES EQUIPMENT <br />CPU CENTRAL PROCESSING UNIT <br />CSA CANADIAN STANDARDS ASSOCIATION <br />CSMA/CA CARRIER SENSE MULTIPLE ACCESS/COLLISION AVOIDANCE <br />CSMA/CD CARRIER SENSE MULTIPLE ACCESS/COLLISION DETECTION <br />GENERAL TELECOMMUNICATIONS LEGEND <br />STANDARD 1-PORT TELECOMMUNICATIONS OUTLET. INSTALL (1) 8P8C MODULAR JACK INSERT INTO (1) 2-PORT SINGLE GANG FACEPLATE. INSTALL (1) <br />DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. INSTALL BLANK INSERTS IN ALL <br />UNUSED PORTS. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS DETAILS FOR <br />MORE INFORMATION. <br />STANDARD 2-PORT TELECOMMUNICATIONS OUTLET. INSTALL (2) 8P8C MODULAR JACK INSERTS INTO (1) 2-PORT SINGLE GANG FACEPLATE. INSTALL (1) <br />DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. COORDINATE MOUNTING <br />HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />STANDARD 4-PORT TELECOMMUNICATIONS OUTLET. INSTALL (4) 8P8C MODULAR JACK INSERTS INTO (1) 4-PORT SINGLE GANG FACEPLATE. INSTALL (1) <br />DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. COORDINATE MOUNTING <br />HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />2 <br />TV <br />FF <br />2 <br />IPC <br />WL <br />FB2 <br />FB4 <br />STANDARD 2-PORT CATV OUTLET. INSTALL (1) 8P8C MODULAR JACK INSERT AND (1) F-CONNECTOR INSERT INTO (1) 2-PORT SINGLE GANG FACEPLATE. <br />INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. INSTALL (1)RG-6 <br />CABLE FOR EACH F-CONNECTOR INSERT INSTALLED. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO <br />COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />WALL MOUNTED FURNITURE FEED. PROVIDE (2) 1-1/4" CONDUITS FROM WALL MOUNTED BOX TO CABLE SUPPORT SYSTEM. PROVIDE FLEXIBLE <br />TECHFLEX NYLON BRAIDING SLEEVE MATERIAL FROM THE COVER PLATE TO FURNITURE ACCESS LOCATION. <br />STANDARD 2-PORT CEILING MOUNTED TELECOMMUNICATIONS OUTLET. INSTALL (2) 8P8C MODULAR JACK INSERTS INTO (1) 4-PORT SINGLE GANG <br />FACEPLATE MOUNTED ON BACKBOX. INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSTALLED. TERMINATE ALL 8 <br />CONDUCTORS. COORDINATE MOUNTING LOCATION WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS DETAILS FOR <br />MORE INFORMATION. <br />STANDARD 1-PORT CEILING MOUNTED IP CAMERA OUTLET. INSTALL (1) 8P8C MODULAR JACK INSERTS INTO (1) 2-PORT SURFACE MOUNTED DEVICE BOX <br />MOUNTED IN BACKBOX. INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 <br />CONDUCTORS. INSTALL BLANK INSERT IN ALL UNUSED PORTS. COORDINATE MOUNTING LOCATION WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. <br />REFER TO COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />STANDARD 2-PORT CEILING MOUNTED WIRELESS ACCESS POINT OUTLET. INSTALL (2) 8P8C MODULAR JACK INSERTS INTO (1) 2-PORT SURFACE <br />MOUNTED DEVICE BOX WITHIN WIRELESS ACCESS POINT ENCLOSURE. INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK <br />INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. COORDINATE MOUNTING LOCATION WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER <br />TO COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />STANDARD PATHWAY OUTLET. PROVIDE (1) 1" CONDUIT WITH 4-11/16" X 4-11/16" X 3" DEEP BACKBOX WITH 1G DEVICE PLATE STUBBED ABOVE <br />ACCESSIBLE CEILING. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS <br />DETAILS FOR MORE INFORMATION. <br />STANDARD 2-PORT FLOOR BOX TELECOMMUNICATIONS OUTLET. INSTALL (2) 8P8C MODULAR JACK INSERTS INTO (1) 2-PORT MOUNTING BRACKET IN <br />DESIGNATED FLOORBOX LOCATION. INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 <br />CONDUCTORS. COORDINATE FINAL LOCATION WITH ARCHITECTURAL DIMENSIONED DRAWINGS PRIOR TO ROUGH-IN. REFER TO ELECTRICAL DRAWINGS <br />FOR MORE INFORMATION. TELECOMMUNICATIONS CONTRACTOR TO PROVIDE MOUNTING BRACKET AND BEZEL IN FLOOR BOX DEVICE PROVIDED BY <br />ELECTRICAL CONTRACTOR. COORDINATE IN FIELD. <br />STANDARD 4-PORT FLOOR BOX TELECOMMUNICATIONS OUTLET. INSTALL (4) 8P8C MODULAR JACK INSERTS INTO (1) 4-PORT MOUNTING BRACKET IN <br />DESIGNATED FLOORBOX LOCATION. INSTALL (1) DEDICATED UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 <br />CONDUCTORS. COORDINATE FINAL LOCATION WITH ARCHITECTURAL DIMENSIONED DRAWINGS PRIOR TO ROUGH-IN. REFER TO ELECTRICAL DRAWINGS <br />FOR MORE INFORMATION. TELECOMMUNICATIONS CONTRACTOR TO PROVIDE MOUNTING BRACKET AND BEZEL IN FLOOR BOX DEVICE PROVIDED BY <br />ELECTRICAL CONTRACTOR. COORDINATE IN FIELD. <br />FF PT FLOOR MOUNTED FURNITURE FEED, POKE THRU. PROVIDE (1) 2" CONDUIT TO CABLE SUPPORT SYSTEM OF FLOOR BEING SERVED. CABLING SHOULD NOT <br />BE RUN IN CABLE SUPPORT SYSTEM ON FLOOR BELOW. PROVIDE FLEXIBLE TECHFLEX NYLON BRAIDING SLEEVE MATERIAL FROM THE COVER PLATE TO <br />FURNITURE ACCESS LOCATION. <br />GENERAL DEMOLITION NOTES: <br />1.REFER TO ARCHITECTURAL DRAWINGS FOR THE FULL EXTENT OF THE SCOPE OF WORK. THE TECHNOLOGY SCOPE OF WORK MAY <br />EXTEND BEYOND THE AREA DEFINED BY THE ARCHITECTURAL DEMOLITION PLANS TO FULLY COMPLY WITH VARIOUS <br />REQUIREMENTS DEFINED BY THESE NOTES. <br />2.THE TECHNOLOGY DEMOLITION PLANS INDICATE THE GENERAL INTENT AND ARE NOT INTENDED TO SHOW ALL ITEMS TO BE <br />REMOVED OR RETAINED. THE TECHNOLOGY CONTRACTOR SHALL VISIT THE SITE PRIOR TO THE SUBMISSION OF BIDS TO BECOME <br />FAMILIAR WITH THE ACTUAL CONDITIONS AND EXTENT OF WORK. DEVICES AND EQUIPMENT LOCATED ON THE WALL AND/OR <br />CEILING TO BE REMOVED SHALL BE DISCONNECTED AND MADE SAFE. THE TECHNOLOGY CONTRACTOR SHALL NOTIFY THE <br />OWNER'S REPRESENTATIVE OF ANY UNANTICIPATED HIDDEN CONDITIONS ENCOUNTERED DURING DEMOLITION. <br />3.THE TECHNOLOGY CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ALL SYSTEMS OR BUILDING COMPONENTS <br />DAMAGED DURING THE EXECUTION OF THE WORK. DAMAGE SHALL INCLUDE BUT NOT BE LIMITED TO DESTRUCTION OR DISPOSAL <br />OF ITEMS INTENDED TO REMAIN OR TO BE SALVAGED. <br />4.THE TECHNOLOGY CONTRACTOR SHALL TRACE AND LABEL ALL EXISTING CABLING WITHIN THE AREA OF DEMOLITION SCOPE OF <br />WORK PRIOR TO DISCONNECTION. <br />5.THE TECHNOLOGY CONTRACTOR SHALL IDENTIFY ALL CABLING AND SYSTEM COMPONENTS WHICH ARE TO REMAIN WITHIN THE <br />AREA OF DEMOLITION SCOPE. THERE SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREA OUTSIDE THE SCOPE LIMITS WITHOUT <br />APPROVAL FROM THE OWNER'S REPRESENTATIVE. EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODE COMPLIANT <br />MANNER. <br />6.THE TECHNOLOGY CONTRACTOR SHALL REMOVE ALL CABLING AND RACEWAYS TO THEIR POINTS OF ORIGIN WITHIN THE AREA OF <br />DEMOLITION SCOPE. ITEMS IDENTIFIED FOR DEMOLITION SHALL NOT BE ABANDONED IN PLACE. RACEWAY THAT ENTER MASONRY <br />WALLS OR FLOORS SHALL BE CUT FLUSH AT THE SURFACE FOR PATCHING BY OTHERS. <br />7.THE TECHNOLOGY CONTRACTOR SHALL TEMPORARILY SUPPORT ALL LOW VOLTAGE CABLING AND ASSOCIATED ITEMS TO REMAIN <br />THAT ARE AFFECTED BY DEMOLITION OF THE BUILDING STRUCTURAL COMPONENTS (WALL, CEILINGS, ETC.) TEMPORARY <br />SUPPORTED ITEMS SHALL BE PERMANENTLY SUPPORTED AND INSTALLED WHEN FINALIZED STRUCTURES ARE IN PLACE. <br />8.ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FOR USE. THE OWNER'S REPRESENTATIVE SHALL <br />INSPECT ALL RETAINED ITEMS PRIOR TO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY TECHNOLOGY CONTRACTOR. <br />9.COORDINATE WITH GENERAL, MECHANICAL, PLUMBING, AND ELECTRICAL CONTRACTORS FOR EXISTING EQUIPMENT TO BE <br />REMOVED. DISCONNECT AND REMOVE ANY TECHNOLOGY DEVICES PRIOR TO EQUIPMENT BEING REMOVED. <br />10.THE CONTRACTOR SHALL PROVIDE BLANK METAL PLATES FOR ALL JUNCTION/DEVICE BOXES NO LONGER IN USE. <br />11.ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE GENERAL CONTRACTOR TO MINIMIZE <br />DISRUPTION TO THE NORMAL DAILY FUNCTIONING OF THE OCCUPIED. <br />12.ALL NON-ATTACHED ITEMS, SUCH AS MOBILE EQUIPMENT, DESKTOP PC OR PHONES SHALL BE REMOVED BY OWNER PRIOR TO <br />COMMENCEMENT OF DEMOLITION WORK. <br />13.UPON COMPLETION, CLEAN ALL AREAS AND REMOVE ALL DEMOLITION MATERIALS, CLEAN ALL ADJACENT AREA AFFECTED BY <br />DEMOLITION. <br />14.ALL NETWORK EQUIPMENT AND WIRELESS ACCESS POINTS SHALL BE REMOVED BY OWNER PRIOR TO COMMENCEMENT OF <br />DEMOLITION WORK. <br />DEMOLITION KEYNOTES: <br />REMOVE ALL EXISTING NURSE CALL DEVICES WITHIN THE LIMIT OF WORK COMPLETELY BACK TO THE POINT OF ORIGIN. <br />CABLING AND RACEWAY TO BE DISPOSED OF PROPERLY. NURSE CALL DEVICES, CONTROLLERS, POWER SUPPLIES ARE TO BE <br />TURNED OVER TO OWNER. DECOMMISSION OR BY-PASS ALL NURSE CALL DEVICES TO BE REMOVED PRIOR TO <br />COMMENCEMENT OF WORK. <br />1 <br />REMOVE ALL EXISTING OVERHEAD PAGING SYSTEMS WITHIN THE LIMIT OF WORK BACK TO THE LOCAL PAGING EQUIPMENT <br />HEAD-END. SPEAKERS, BACK BOXES, CABLING AND RACEWAY TO BE DISPOSED OF PROPERLY. COORDINATE EXISTING PAGING <br />SYSTEM WITH OWNER STAFF TO MAINTAIN PAGING FEED, CABLE OR CONNECTING PAGING ZONES. <br />2 <br />REMOVE ALL EXISTING TELECOMMUNICATIONS, SECURITY, VIDEO SURVEILLANCE AND INTERCOM DEVICES WITHIN THE LIMIT <br />OF WORK COMPLETELY BACK TO POINT OF ORIGIN. CABLING AND RACEWAY TO BE DISPOSED OF PROPERLY. EXISTING PATCH <br />PANELS TO BE REMOVED FROM EXISTING COMMUNICATIONS ROOMS ARE TO BE TURNED OVER TO THE OWNER AT A LOCATION <br />DESIGNATED BY OWNER. REFER TO ARCHITECTURAL DEMOLITION PLANS FOR EXACT SCOPE OF WORK TO BE DEMOLISHED. <br />3 <br />EXISTING DAS INSTALLATION SHALL BE REMOVED/REPLACED BY OWNERS DAS INSTALLATION VENDOR. COORDINATE WITH <br />OWNER PRIOR TO START OF WORK. <br />4 <br />THE TELECOMMUNICATIONS CONTRACTOR SHALL COORDINATE TEMPORARY REMOVAL OF ALL CEILING MOUNTED <br />TECHNOLOGY DEVICES WITHIN THE AREA OF WORK WHERE REQUIRED FOR ANY CEILING REMOVAL. UPON COMPLETION OF <br />ABOVE CEILING WORK, REINSTALL AND RECONNECT DEVICES AS REQUIRED BACK TO CURRENT CONDITION. <br />5 <br />STANDARD ROOM SCHEDULER OUTLET. INSTALL (2) 8P8C MODULAR JACK INSERTS INTO (1) 2-PORT SINGLE GANG FACEPLATE. INSTALL (1) DEDICATED <br />UTP CATEGORY CABLE FOR EACH 8P8C MODULAR JACK INSERT INSTALLED. TERMINATE ALL 8 CONDUCTORS. COORDINATE MOUNTING HEIGHT WITH <br />ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. REFER TO COMMUNICATIONS DETAILS FOR MORE INFORMATION. <br />RS <br />1423 <br />A <br />C <br />B <br />1423 <br />A <br />C <br />SHEET NUMBER <br />TITLE <br />Approved <br />Checked <br />Drawn <br />Job Number <br />ISSUE CHART <br />CONSULTANTS <br />KEYPLAN <br />PROJECT <br />B <br />FIRM CERTIFICATION C.A #6057 <br />ERIK S WALKER P.E: #63929 <br />JOHN MOUDLER P.E: #33200 <br />CARLOS E. JIMENEZ P.E: #47923 <br />RICARDO DURAN P.E: #64768 <br />GLEN R. SEILER P.E: #83347 <br />BR+A CONSULTING ENGINEERS <br />2600 DOUGLAS ROAD, SUITE 1100 <br />CORAL GABLES, FL 33134 <br />THORNTON TOMASETTI <br />101 NE THIRD AVENUE, SUITE 1170 <br />FORT LAUDERDALE, FL 3330` <br />f.954.903.9300 <br />f 954.903 9301 <br />ESI CONSULTING ENGINEERS, INC <br />1315 NW 98TH CT. <br />UNIT 15, DORAL, FL 33172 <br />t. 305.418.9177 <br />t 305.418.9178 <br />HVAC <br />STRUCTURAL ENGINEERS <br />ELECTRICAL + PLUMBING <br />INMAN FOODSERICE GROUP <br />1330 CORAL WAY <br />SUITE 310 <br />MIAMI, FL 33145 <br />FOOD SERVICE <br />PE <br />R <br />M <br />I <br />T <br /> <br />S <br />E <br />T <br /> <br />1 <br />2 <br />. <br />0 <br />6 <br />. <br />1 <br />8 <br />1 2 /4 /2 0 1 8 8 :0 7 :4 9 A M <br />C :\_R e v i t \T E C H - G A T E W A Y - v 2 0 1 8 _a v i l l a n u e v a C B Y X V .r v t <br />T00-01 <br />COMMUNICATIONS <br />LEGEND <br />JJP <br />AMV <br />810495.000 <br />JJP <br />SIB -GATEWAY <br />PARK <br />Copyright © 2018 Perkins+Will <br />PROJECT ADDRESS: <br />151 Sunny Isles Blvd <br />Sunny Isles Beach, FL <br />33160 <br />2800 Ponce De Leon Blvd <br />Suite 1300 <br />Coral Gables, FL 33134 <br />t 305.569.1333 <br />f 305.569.1334 <br />www.perkinswill.com <br />NO.ISSUE DATE <br />PERMIT SET 12.06.2018
The URL can be used to link to this page
Your browser does not support the video tag.