Laserfiche WebLink
TYPICAL WIDE BASE, J- <br />HOOK CABLE <br />MANAGEMENT (SEE <br />SPEC) <br />FASTENER NUT <br />1/4" THREADED <br />ROD <br />ANCHOR BRACKET <br />CABLE MANAGEMENT TIE <br />(TYPICAL ALL J-HOOKS) <br />STRUCTURE ABOVE <br />ACCESSIBLE CEILING <br />NOTES: <br />1.J-HOOKS SHALL BE MOUNTED EVERY 48" to 60"; O.C. MINIMUM AND ACCESSIBLE AT ALL TIMES. MAINTAIN <br />MINIMUM OF 6" OF CLEARANCE FROM CEILING TILES AND OTHER OBSTRUCTIONS. <br />2.J-HOOK PATHWAY MUST BE CONTINUOUS. ALL J-HOOKS SHALL BE MOUNTED ABOVE CEILING AT AN <br />ACCESSIBLE AREA. AREAS THAT ARE NOT ACCESSIBLE SHALL TRANSITION TO A CONDUIT PATHWAY. <br />3.MALLEABLE BEAM CLAMP METHOD OF HANGING J-HOOKS SHALL BE ACCEPTED WHEN HANGING OFF OF <br />STRUCTURAL STEEL ONLY. <br />4.DO NOT MOUNT J-HOOKS TO SUPPORT BEAMS OR STRUCTURES THAT HAVE SPRAYED-ON FIRE <br />PROOFING MATERIAL. MOUNTING SUPPORT HOOKS MUST NOT DISTURB THE FIRE RATING OF ANY <br />STRUCTURE. <br />SECURE TRAY TO <br />PLYWOOD BACKER BOARD <br />CABLE RUNWAY <br />DISTRIBUTION SYSTEM <br />PARTITION -SEE <br />ARCHITECTURAL <br />DRAWINGS <br />SLEEVES FOR HORIZONTAL <br />CABLING -SEE PLAN <br />FINISHED FLOOR -SEE PLAN <br />TYPICAL IDF <br />ROOM <br />ACCESSIBLE CEILING - <br />SEE RCP <br />INACCESSIBLE CEILING - <br />SEE RCP <br />J-HOOK CABLE SUPPORT <br />SYSTEM WITH 1/4" THREADED <br />ROD (TYPICAL) <br />PROVIDE THREADED, <br />INSULATED BUSHINGS <br />EACH END OF SLEEVE <br />(TYPICAL) <br />EXTEND SLEEVES AND CONDUITS <br />BEYOND PARTITION WALL INTO <br />ROOM A MIN. OF 3-INCHES - <br />TRANSITION DISTANCE <br />(SEPARATION) BETWEEN SLEEVES <br />OR CONDUITS AND <br />COMMUNICATION ROOM RUNWAY <br />SYSTEM SHALL NOT EXCEED 6- <br />INCHES <br />INACCESSIBLE CEILING OR SOFFIT AREA <br />1" CONDUIT WITH PULL STRING TO ABOVE <br />ACCESSIBLE CEILING TO LOCAL CABLE TRAY <br />SUPPORT SYSTEM IN THE MAIN AND <br />SECONDARY CORRIDORS ON THE FLOOR. <br />PARTITION WALL <br />DEVICE BOX <br />ACCESSIBLE CEILING <br />FINISHED FLOOR <br />CEILING SLAB OR SUPPORT <br />TYPICAL COMMUNICATIONS FACEPLATE <br />HORIZONTAL DISTRIBUTION CABLE FROM <br />WORK AREA OUTLET TO NEAREST <br />TECHNOLOGY DISTRIBUTION ROOM (TDR) <br />1. AT ALL TECHNOLOGY OUTLETS, CONDUIT SHALL BE <br />INSTALLED FROM EACH DEVICE BACKBOX TO <br />NEAREST ACCESSIBLE CEILING AREA CONTAINING A <br />CABLE TRAY SUPPORT SYSTEM IN MAIN OR <br />SECONDARY CORRIDOR ON THE FLOOR. CABLE <br />ROUTED ABOVE INACCESSIBLE OR "HARD" CEILINGS <br />SHALL BE INSTALLED IN CONDUIT. <br />GENERAL NOTES: <br />CO <br />O <br />R <br />D <br />I <br />N <br />A <br />T <br />E <br /> <br />W <br />I <br />T <br />H <br />AR <br />C <br />H <br />I <br />T <br />E <br />C <br />T <br />U <br />R <br />A <br />L <br />DR <br />A <br />W <br />I <br />N <br />G <br />S <br />TERMINATE CONDUIT ON CABLE TRAY <br />TYPICAL CABLE TRAY <br />THREADED, INSULATED BUSHING (TYPICAL) <br />T40-02 <br />5 <br />T40-03 <br />4 <br />TYPICAL WIRE BASKET <br />CABLE TRAY DISTRIBUTION <br />SYSTEM <br />3/8" DIAMETER THREADED ROD <br />THREADED ROD PROTECTOR <br />HEAVY DUTY/SUPPORT <br />CHANNEL/HANGER ASSEMBLY. <br />(1-5/8" UNISTRUT EVERY 60") <br />CONDUIT CONNECTOR TO WIRE <br />BASKET CABLE TRAY <br />1" CONDUIT FROM WORK AREA OUTLET <br />INACCESSIBLE CEILING OR SOFFIT AREA <br />1" CONDUIT WITH PULL STRING TO ABOVE <br />ACCESSIBLE CEILING TO LOCAL J-HOOK <br />SUPPORT SYSTEM IN THE MAIN OR <br />SECONDARY CORRIDOR ON THE FLOOR. <br />PARTITION WALL <br />DEVICE BOX <br />ACCESSIBLE CEILING <br />FINISHED FLOOR <br />CEILING SLAB OR SUPPORT <br />TYPICAL COMMUNICATIONS FACEPLATE <br />HORIZONTAL DISTRIBUTION CABLE FROM <br />WORK AREA OUTLET TO TECHNOLOGY <br />DISTRIBUTION ROOM (TDR) <br />1.AT ALL TECHNOLOGY OUTLETS, CONDUIT SHALL <br />BE INSTALLED FROM EACH DEVICE BACKBOX TO <br />NEAREST ACCESSIBLE CEILING AREA <br />CONTAINING A J-HOOK CABLE SUPPORT SYSTEM <br />IN MAIN OR SECONDARY CORRIDOR ON FLOOR. <br />CABLE ROUTED ABOVE INACCESSIBLE OR "HARD" <br />CEILINGS SHALL BE INSTALLED IN CONDUIT. <br />GENERAL NOTES: <br />CO <br />O <br />R <br />D <br />I <br />N <br />A <br />T <br />E <br /> <br />WI <br />T <br />H <br />AR <br />C <br />H <br />I <br />T <br />E <br />C <br />T <br />U <br />R <br />A <br />L <br />DR <br />A <br />W <br />I <br />N <br />G <br />S <br />TERMINATE CONDUIT WITHIN 6" <br />OF CABLE SUPPORT SYSTEM <br />THREADED, INSULATED BUSHING (TYPICAL) <br />J-HOOK CABLE SUPPORT SYSTEM WITH <br />1/4" THREADED ROD (TYPICAL) <br />48" TO 60" ON CENTER <br />T40-02 <br />5 <br />1423 <br />A <br />C <br />B <br />1423 <br />A <br />C <br />SHEET NUMBER <br />TITLE <br />Approved <br />Checked <br />Drawn <br />Job Number <br />ISSUE CHART <br />CONSULTANTS <br />KEYPLAN <br />PROJECT <br />B <br />FIRM CERTIFICATION C.A #6057 <br />ERIK S WALKER P.E: #63929 <br />JOHN MOUDLER P.E: #33200 <br />CARLOS E. JIMENEZ P.E: #47923 <br />RICARDO DURAN P.E: #64768 <br />GLEN R. SEILER P.E: #83347 <br />BR+A CONSULTING ENGINEERS <br />2600 DOUGLAS ROAD, SUITE 1100 <br />CORAL GABLES, FL 33134 <br />THORNTON TOMASETTI <br />101 NE THIRD AVENUE, SUITE 1170 <br />FORT LAUDERDALE, FL 3330` <br />f.954.903.9300 <br />f 954.903 9301 <br />ESI CONSULTING ENGINEERS, INC <br />1315 NW 98TH CT. <br />UNIT 15, DORAL, FL 33172 <br />t. 305.418.9177 <br />t 305.418.9178 <br />HVAC <br />STRUCTURAL ENGINEERS <br />ELECTRICAL + PLUMBING <br />INMAN FOODSERICE GROUP <br />1330 CORAL WAY <br />SUITE 310 <br />MIAMI, FL 33145 <br />FOOD SERVICE <br />PE <br />R <br />M <br />I <br />T <br /> <br />S <br />E <br />T <br /> <br />1 <br />2 <br />. <br />0 <br />6 <br />. <br />1 <br />8 <br />1 2 /4 /2 0 1 8 8 :0 8 :0 5 A M <br />C :\_R e v i t \T E C H - G A T E W A Y - v 2 0 1 8 _a v i l l a n u e v a C B Y X V .r v t <br />T40-03 <br />COMMUNICATIONS <br />DETAILS <br />JJP <br />AMV <br />810495.000 <br />JJP <br />SIB -GATEWAY <br />PARK <br />Copyright © 2018 Perkins+Will <br />PROJECT ADDRESS: <br />151 Sunny Isles Blvd <br />Sunny Isles Beach, FL <br />33160 <br />12" = 1'-0"1 TYPICAL WIDE AREA J-HOOK DETAIL <br />N.T.S.2 IDF/MDF CABLE SUPPORT SYSTEM TRANSITION <br />2800 Ponce De Leon Blvd <br />Suite 1300 <br />Coral Gables, FL 33134 <br />t 305.569.1333 <br />f 305.569.1334 <br />www.perkinswill.com <br />N.T.S.3 CONDUIT/BACKBOX WALL DEVICE DETAIL - CABLE TRAY <br />N.T.S.4 TYPICAL WIRE BASKET CONDUIT CONNECTION DETAIL <br />N.T.S.5 WALL DEVICE DETAIL - J-HOOK <br />NO.ISSUE DATE <br />PERMIT SET 12.06.2018