1.INSTALL CONDUIT RUNS IN THE MOST DIRECT ROUTE POSSIBLE WITH NO MORE THAN TWO 90 DEGREE BENDS BETWEEN PULL POINTS OR PULL <br />BOXES. <br />2.90 DEGREE CONDUITS "LB" TYPE FITTINGS SHALL NOT BE USED FOR TELEAV CABLING INSTALLATIONS. <br />3.CONTINUOUS CONDUIT SECTIONS OR SEGMENTS SHALL NOT BE GREATER THAN 100 LINEAR FEET IN LENGTH WITHOUT AN ADEQUATELY SIZED <br />PULL BOX -REFER TO DETAIL <br />4.CONDUITS SHALL BE BONDED TO GROUND ON ONE OR BOTH ENDS IN ACCORDANCE WITH NATIONAL AND LOCAL REQUIREMENTS. <br />5.AV CONDUITS SHALL BE INSTALLED TO WITHSTAND THE ENVIRONMENT IN WHICH THEY WILL BE EXPOSED AND IN ACCORDANCE WITH <br />ANSI/NFPA-70; THE NATIONAL ELECTRICAL CODE. <br />6.THE TOTAL DISTANCE OF CONDUIT RUNS FOR AV HORIZONTAL CABLE USE SHALL NOT EXCEED 150 FEET. <br />7.DO NOT INSTALL CONDUITS OVER OR ADJACENT TO BOILERS, INCINERATORS, HOT WATER OR STEAM LINES. <br />8.THE MINIMUM BEND RADIUS OF ANY PORTION OF THE CONDUIT PATHWAY SHALL BE SIX (6) TIMES THE INTERNAL DIAMETER OF THE CONDUIT <br />FOR ALL CONDUITS 2-INCHES IN DIAMETER OR LESS. <br />9.THE MINIMUM BEND RADIUS OF ANY PORTION OF THE CONDUIT PATHWAY SHALL BE TEN (10) TIMES THE INTERNAL DIAMETER OF THE CONDUIT <br />FOR ALL CONDUITS WITH AN INTERNAL DIAMETER GREATER THAN 2-INCHES. <br />10.WHERE A CONDUIT RUN REQUIRES A REVERSE BEND (BETWEEN 100 DEGREES AND 180 DEGREES) A PULL BOX SHALL BE INSTALLED AT EACH <br />BEND HAVING SUCH ANGLE, WITHIN 10 FEET OF THE BEND. <br />11.IF A CONDUIT RUN REQUIRES A THIRD 90 DEGREE BEND BETWEEN PULL POINTS OR PULL BOX, THE OVERALL DESIGN CAPACITY OF THE CONDUIT <br />SYSTEM SHALL HAVE A DERATED TOTAL CAPACITY OF 15 PERCENT. <br />12.ALL CONDUIT ENDS SHALL BE REAMED AND FITTED WITH THREADED INSULATING BUSHING TO ELIMINATE SHARP EDGES THAT CAN DAMAGE <br />CABLES DURING INSTALLATION. <br />13.CONDUITS THAT PROTRUDE THROUGH WALLS AND FLOORS SHALL BE EXTENDED BEYOND THE SURFACE PENETRATION TO WITHIN 12 INCHES <br />OF THE CABLE TRAY OR CABLE RUNWAY SYSTEM. <br />14.ALL AV OUTLETS STUB-UPS SHALL BE EQUIPPED WITH A PULL STRING WITH A MINIMUM TEST RATING OF 200 LBS. <br />15.ALL INTERIOR AV CONDUITS GREATER THAN 1 1/2" CONDUITS SHALL BE EQUIPPED WITH 1/2" CABLE PULL STRING WITH 1250 LBS OF TENSILE <br />STRENGTH AND SEQUENTIAL FOOTAGE MARKING. <br />16.ALL EXTERIOR AV CONDUITS SHALL BE EQUIPPED WITH 1/2" CABLE PULL STRING WITH 1250 LBS OF TENSILE STRENGTH AND SEQUENTIAL <br />FOOTAGE MARKING. <br />17.INSTALL PULL BOXES IN ACCESSIBLE LOCATIONS. DIRECT ACCESS TO PULL BOXES IS REQUIRED. PROVIDE LABELED, HINGED ACCESS PANEL <br />DOOR. PULL BOXES SHALL BE LISTED FOR THE PURPOSE. <br />18.THE MINIMUM LENGTH OF PULL BOX SHALL BE 12 TIMES THE DIAMETER OF THE LARGEST CONDUIT. PULL BOXES SHALL NOT BE USED IN <br />SUBSTITUTION OF A 90 DEGREE BEND. <br />19.REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING ELEVATIONS. <br />20.REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR COORDINATION OF ALL CONDUIT, RUNWAY, AND TRAY. <br />21.COORDINATE EXACT LOCATIONS OF ALL FLOOR BOXES AND POKE-THRU DEVICES WITH ARCHITECT PRIOR TO INSTALLATION. <br />22.ALL OUTLET LOCATIONS AND DIMENSIONS ARE APPROXIMATE. COORDINATE EXACT MOUNTING LOCATION AND HEIGHT WITH ARCHITECTURAL <br />DRAWINGS PRIOR TO INSTALLATION. <br />23.WHERE CABLE TRAY RUNS ARE OBSTRUCTED, J-HOOKS MAY BE USED. J-HOOKS SHALL BE SPACED NO LESS THAN 48" O.C AND NOT GREATER <br />THAN 60" O.C. WHERE AV CABLE AND SECURITY CABLE FOLLOW THE SAME PATH, CABLES SHALL BE SEPARATED. ALL AV OUTLETS SHOWN IN <br />OPEN AIR ENVIRONMENT (I.E. MECHANICAL SPACE, PENTHOUSE, ROOF, GARAGE) SHALL BE INSTALLED IN CONDUIT, RATED FOR THAT <br />ENVIRONMENT. <br />24.ALL AV HORIZONTAL STRUCTURED CABLING SHALL BE INSTALLED IN MAIN AND SECONDARY CORRIDORS ONLY FROM AV ROOM TO WORK AREA <br />OUTLETS. <br />25.ALL AV HORIZONTAL STRUCTURED CABLING SHALL ENTER WORK AREA ROOMS VIA PROPERLY SIZED CONDUIT ABOVE DOOR. CONDUIT SLEEVE <br />SHALL BE PROPERLY FIRESTOPPED TO MAINTAIN FIRE RATING. <br />26.UNDER NO CIRCUMSTANCES SHALLAV HORIZONTAL STRUCTURED CABLING BE INSTALLED THROUGH ADJACENT ROOMS TO WORK AREA <br />OUTLETS. <br />GENERAL PATHWAY REQUIREMENTS <br />POI POINT OF INTERFACE <br />POTS PLAIN OLD TELEPHONE SERVICE <br />PR PAIR <br />PTSS PASSIVE TRANSMISSION SUBSYSTEM <br />PVC POLYVINYL CHLORIDE <br />SE SERVICE ENTRANCE <br />SER SATELLITE EQUIPMENT ROOM <br />SI SYSTEM INTERNATIONAL <br />SL SLEEVE <br />SMPS SWITCHED MODE POWER SUPPLY <br />SNA SYSTEMS NETWORK ARCHITECTURE <br />SP SERVICE PROVIDER <br />SPC STORED PROGRAM CONTROL <br />SPD SURGE PROTECTION DEVICE <br />SPG SINGLE-POINT GROUND <br />STA STATION <br />STP SHIELDED TWISTED PAIR <br />SW STATION WIRE <br />SWB SWITCHBOARD <br />SYS SYSTEM <br />TB TERMINAL BLOCK <br />TBBC TELECOMMUNICATIONS BACKBONE BONDING CONDUCTOR <br />TBC TELECOMMUNICATION BONDING CONDUCTOR <br />TC TELECOMMUNICATIONS CLOSET <br />TDM TIME DIVISION MULTIPLEXING <br />TEBC TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR <br />TEL TELEPHONE <br />TELCO TELEPHONE COMPANY <br />TERM TERMINAL <br />TGB TELECOMMUNICATIONS GROUNDING BUSBAR <br />THD TOTAL HARMONIC DISTORTION <br />TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION <br />TM TRANSFORMER MAINTENANCE HOLE <br />TMGB TELECOMMUNICATIONS MAIN GROUNDING BUSBAR <br />TO TELECOMMUNICATIONS OUTLET <br />TPDDI TWISTED PAIR DISTRIBUTED DATA INTERFACE <br />TPPMD TWISTED PAIR PHYSICAL MEDIUA DEPENDENT <br />TR TELECOMMUNICATIONS ROOM <br />TSB TELECOMMUNICATIONS SYSTEM BULLETIN <br />TT TELEPHONE TERMINAL <br />TTB TELEPHONE TERMINAL BOARD <br />TTY TEXT TELEPHONES <br />TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR <br />TYP TYPICAL <br />UG UNDERGROUND <br />UL UNDERWRITERS LABORATORIES <br />UPS UNINTERRUPTIBLE POWER SUPPLY <br />UTP UNSHIELDED TWISTED PAIR <br />ISDN INTEGRATED SERVICES DIGITAL NETWORK <br />ISO INTEGRATED STANDARDS ORGANIZARION <br />IW INSIDE WIRING (CABLE) <br />KHz KILOHERTZ <br />KTS KEY TELEPHONE SYSTEM <br />LAN LOCAL AREA NETWORK <br />LASER LIGHT AMPLIFICATION BY STIMULATED EMISSION OF RADIATION <br />LATA LOCAL ACCESS TRANSPORT AREA <br />LBO LINE BUILDOUT <br />LEC LOCAL EXCHANGE CARRIER <br />LED LIGHT EMITTING DIODE <br />LOCAP LOW CAPACITANCE <br />MAP MANUFACTURING AUTOMATION/PROTOCOL <br />MAX MAXIMUM <br />MC MAIN CROSS-CONNECT <br />MDF MAIN DISTRIBUTION FRAME <br />M/G MOTOR/GENERATOR SET <br />MH MAINTENANCE HOLE <br />MICRON MICROMETER <br />MIN MINIMUM <br />MISC MISCELLANEOUS <br />MODEM MODULATOR/DEMODULATOR <br />MPOP MINIMUM POINT OF PRESENCE <br />MTT MAIN TELEPHONE TERMINAL <br />N NEWTON <br />NEC NATIONAL ELECTRIC CODE <br />NESC NATIONAL ELECTRIC SAFETY CODE <br />NI NETWORK INTERFACE <br />NIC NOT IN CONTRACT <br />NID NETWORK INTERFACE DEVICE <br />NIU NETWORK INTERFACE UNIT <br />NRTL NATIONALLY RECOGNIZED TESTING LABORATORY <br />NTS NOT TO SCALE <br />OC ON CENTER <br />OD OUTSIDE DIAMETER <br />OFNP OPTICAL FIBER NON-CONDUCTIVE PLENUM <br />OFNR OPTICAL FIBER NON-CONDUCTIVE RISER <br />OPD OVERCURRENT PROTECTION DEVICE <br />OPE OUTSIDE PLANT ENGINEER <br />OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION <br />OSP OUTSIDE PLANT <br />PAM PULSE AMPLITUDE MODULATE <br />PB PULL BOX <br />PBX PRIVATE BRANCH EXCHANGE <br />PCM PULSE CODE MODULATION <br />PIC POLYETHYLENE INSULATED CONDUCTOR <br />PL PRIVATE LINES <br />PLT PLANT <br />PM PHASE MODULATION <br />D/A DIGITAL TO ANALOG CONVERSION <br />DAF DEDICATED ACCESS FACILITY <br />DB DECIBEL <br />DC DIRECTED CURRENT <br />DCE DATA CIRCUIT-TERMINATION EQUIPMENT <br />DCO DIGITAL CENTRAL OFFICE <br />DD DISTRIBUTION DESIGNER <br />DEMARC DEMARCATION POINT <br />DGM DATA GRADE MEDIUM <br />DTE DATA TERMINAL EQUIPMENT <br />DW DISTRIBUTION WIRE <br />DWG DRAWING(S) <br />EBC EQUIPMENT BONDING CONDUCTOR <br />EC ELECTRICAL CONTRACTOR <br />EF ENTRANCE FACILITY <br />EIA ELECTRONICS INDUSTRY ASSOCIATION <br />ELEC ELECTRICAL <br />EMC ELECTROMAGNETIC COMPATABILITY <br />EMI ELECTROMAGNETIC INTERFACE <br />EMR ELECTROMAGNETIC RADIATION <br />EMT ELECTRICAL METALLIC TUBING <br />ESS ELECTRONIC SWITCHING SYSTEM <br />ETV EDUCATIONAL TELEVISION <br />E/W EQUIPPED WITH <br />EXCH EXCHANGE <br />EXT EXTENSION <br />FCC FEDERAL COMMUNICATIONS COMMISSION <br />FD FLOOR DISTRIBUTION <br />FDDI FIBER DISTRIBUTION DATA INTERFACE <br />FDM FREQUENCY DIVISION MULTIPLEXING <br />FDR FEEDER <br />FO FIBER OPTIC <br />FOTP FIBER OPTIC TRANSMISSION SYSTEM <br />FREQ FREQUENCY <br />FTP FOIL TWISTED PAIR <br />GA GAUGE <br />GEC GROUNDING ELECTRIC CONDUCTOR <br />GHz GIGAHERTZ <br />GND GROUND <br />HC HORIZONTAL CROSS-CONNECT <br />HF HIGH FREQUENCY <br />HH HANDHOLE <br />HVAC HEATING, VENTILATION AND AIR CONDITIONING <br />Hz HERTZ <br />IC INTERMEDIATE CROSS-CONNECT <br />ICEA INSULATED CABLE ENGINEERS ASSOCIATION <br />IDC INSULATION DISPLACEMENT CONNECTION <br />IDF INTERMEDIATE DISTRIBUTION FRAME <br />IEEE INTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS <br />8P8C 8-POSITION, 8-CONDUCTOR <br />AC ALTERNATING CURRENT <br />A/D ANALOG TO DIGITAL CONVERSION <br />ACO ANALOG CENTRAL OFFICE <br />ADA AMERICANS WITH DISABILITIES ACT <br />ADO AUXILIARY DISCONNECT OUTLET <br />AER AERIAL <br />AFF ABOVE FINISHED FLOOR <br />AIA AMERICAN INSTITUTE OF ARCHITECTS <br />AM AMPLITUDE MODULATION <br />ANSI AMERICAN NATIONAL STANDARDS INSTITUTE <br />ARMM PIC RISER, EXPANDED POLYETHYLENE PVC, 24 AWG, ALVYN <br />ASCII AMERICAN STANDARD CODE FOR INFORMATION INTERCHANGE <br />ATM ASYNCHRONOUS TRANSFER MODE <br />AWG AMERICAN WIRE GAUGE <br />B BURIED <br />BC BONDING CONDUCTOR <br />BBISDN BROADBAND INTEGRATED SERVICES DIGITAL NETWORK <br />BD BUILDING DISTRIBUTOR <br />BDF BUILDING DISTRIBUTION FRAME <br />BEF BUILDING ENTRANCE FACILITY <br />BER BIT ERROR RATE <br />BIC BUILDING INDUSTRY CONSULTANT <br />BICSI BUILDING INDUSTRY CONSULTING SERVICES <br />BRISDN BASIC RATE INTEGRATED SERVICES DIGITAL NETWORK <br />BTU BRITISH THERMAL UNIT <br />CA CABLE <br />CATV CABLE TELEVISION <br />CBC COUPLED BONDING CONDUCTOR <br />CC COMMUNICATIONS CONTRACTOR <br />CCITT THE INTERNATIONAL TELEGRAPH AND TELEPHONE CONSULTATIVE COMMITTEE <br />CD CONDUIT <br />CDDI COPPER DISTRIBUTED DATA INTERFACE <br />CDF COPPER DISTRIBUTION FRAME <br />CDO COMMUNITY DIAL OFFICE <br />CER COMPUTER EQUIPMENT ROOM <br />CIRC CIRCUIT <br />CFC COMMUNICATIONS FLAT CABLE <br />CLO CLOSET <br />CO CENTRAL OFFICE <br />CODEC CODER/DECODER <br />COE CENTRAL OFFICE EQUIPMENT <br />COT CENTRAL OFFICE TERMINAL <br />CPC CUSTOMER PREMISES COMMUNICATIONS <br />CPE CUSTOMER PREMISES EQUIPMENT <br />CPU CENTRAL PROCESSING UNIT <br />CSA CANADIAN STANDARDS ASSOCIATION <br />CSMA/CA CARRIER SENSE MULTIPLE ACCESS/COLLISION AVOIDANCE <br />CSMA/CD CARRIER SENSE MULTIPLE ACCESS/COLLISION DETECTION <br />GENERAL AV LEGEND <br />1.ALL CONFERENCE ROOMS AND MEETING SPACE HVAC EQUIPMENT SHOULD BE DESIGNED FOR A NOISE CRITERION (NC) RATING OF 25-30. <br />2.THE BACK WALL AND AT LEAST ONE SIDE WALL SHOULD BE TREATED WITH ACOUSTIC MATERIAL. NOISE REDUCTION COEFFICIENT (NRC) OF <br />WALL TREATMENTS SHOULD BE A MINIMUM OF .5 (.8 IS DESIRED). <br />3.ALL CONFERENCE ROOM WALLS SHOULD EXTEND AND BE SEALED TO THE DECK ABOVE AND HAVE AN SOUND TRANSMISSION CLASS (STC) <br />RATING OF 50 OR BETTER. CONFERENCE ROOM WALLS ADJACENT TO MECHANICAL ROOMS SHOULD HAVE AN STC RATING OF 60. <br />4.WHERE CONFERENCE ROOMS ARE LOCATED BELOW HIGH IMPACT FLOOR ACTIVITIES SUCH AS FITNESS CENTERS OR BELOW ROOF <br />MECHANICAL EQUIPMENT THE IMPACT INSULATION CLASS (IIC) RATING FOR FLOOR-CEILING ASSEMBLIES SHALL BE A MINIMUM OF 45. WHEN <br />LOCATED ABOVE SUCH SPACES THE IIC RATING SHOULD BE 65 OR BETTER. <br />5.AVOID USING ELECTRONIC MASKING SYSTEMS IN ALL CONFERENCE ROOMS AND MEETING SPACES. WHERE UNAVOIDABLE, SOUND MASKING <br />SPEAKERS SHOULD BE CAPABLE OF BEING INDIVIDUALLY ATTENUATED IN THESE AREAS. <br />ACOUSTIC CONSIDERATIONS FOR CONFERENCE AND MEETING SPACES <br />1.ALL CIRCUITS SHOWN ON THE AV SERIES DRAWINGS ARE FOR REFERENCE ONLY. REFER TO ARCHITECTURAL AND ELECTRICAL DRAWINGS FOR <br />LOCATIONS, MOUNTING HEIGHTS AND POWER REQUIREMENTS. <br />2.ALL CIRCUITS FOR AUDIO VISUAL EQUIPMENT WITHIN A CONFERENCE ROOM OR MEETING SPACE WILL BE ON THE SAME PHASE. <br />3.AVOID RUNNING ELECTRICAL CIRCUIT WIRING FOR MOTORS AND DIMMERS OR OTHER INDUCTIVE LOADS ALONG SIDE AV ELECTRICAL CIRCUIT <br />WIRING. <br />ELECTRICAL CONSIDERATIONS FOR CONFERENCE AND MEETING SPACES <br />SYMBOL DESCRIPTION <br />AV INFRASTRUCURE LEGEND <br />D1 WALL MOUNTED DISPLAY LOCATION, TYPE 1 <br />D2 <br />IN1 <br />TP <br />AV <br />S <br />PJ <br />AP <br />WALL MOUNTED DISPLAY LOCATION, TYPE 2 <br />AV INTERFACE <br />TOUCH PANEL <br />JUNCTION BOX FOR AV EQUIPMENT RACK <br />CEILING MOUNTED SPEAKER <br />CEILING MOUNTED PROJECTOR <br />CEILING MOUNTED ACCESS PANEL <br />BACKBOX AND CONDUIT REQUIREMENTS <br />14" x 14" x 3.88" IN WALL BOX. PROVIDE (1) 1-1/4" CONDUIT FOR AV CABLING, (1) 1-1/4" CONDUIT FOR DATA, AND <br />(1) 1/2" CONDUIT FOR ELECTRICAL. CONDUITS TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR <br />ALL CONDUITS <br />4-11/16" x 4-11/16" x 3-1/2" DEEP BACKBOX WITH SINGLE GANG MUD RING. PROVIDE (1) 1-1/4" CONDUIT FOR AV <br />CABLING TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />D3 WALL MOUNTED DISPLAY LOCATION, TYPE 3 <br />2 GANG, 3-1/2" DEEP BACKBOX. PROVIDE (1) 1-1/4" CONDUIT FOR AV CABLING TO NEAREST ACCESSIBLE <br />CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />12" x 12" x 4" JUNCTION BOX WITH SCREW ON COVER INSTALLED IN WALL. PROVIDE (2) 2" CONDUITS FOR AV <br />CABLING TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />AL ASSISTED LISTENING DEVICE 4-11/16" x 4-11/16" x 3-1/2" DEEP BACKBOX WITH SINGLE GANG MUD RING. PROVIDE (1) 1-1/4" CONDUIT FOR AV <br />CABLING TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />FB <br />FLOOR BOX FLOOR BOX BY ELECTRICAL CONTRACTOR. PROVIDE (1) 1-1/4" CONDUIT FOR AV CABLING TO NEAREST <br />ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />PS CEILING MOUNTED PROJECTION SCREEN <br />SW CEILING MOUNTED SUBWOOFER PROVIDE (1) 1" CONDUIT FROM AV 119 TO EACH SUBWOOFER. PROVIDE PULL STRING FOR ALL CONDUITS. <br />NOTES: <br />1. COORDINATE EXACT MOUNTING HEIGHTS AND LOCATIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN. <br />2. PROVIDE PULL STRING FOR ALL CONDUITS <br />BT WALL MOUNTED BLUETOOTH CONNECTION 4-11/16" x 4-11/16" x 3-1/2" DEEP BACKBOX WITH SINGLE GANG MUD RING. PROVIDE (1) 3/4" CONDUIT FOR AV <br />CABLING TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />9" x 14" x 3.88" IN WALL BOX. PROVIDE (1) 1-1/4" CONDUIT FOR AV CABLING, (1) 1-1/4" CONDUIT FOR DATA, AND (1) <br />1/2" CONDUIT FOR ELECTRICAL. CONDUITS TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL <br />CONDUITS <br />22" x 14" x 3.88" IN WALL BOX. PROVIDE (1) 1-1/4" CONDUIT FOR AV CABLING, (1) 1-1/4" CONDUIT FOR DATA, AND <br />(1) 1/2" CONDUIT FOR ELECTRICAL. CONDUITS TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR <br />ALL CONDUITS <br />PROVIDE (1) 1" CONDUIT FROM AV 119 TO EACH PROJECTION SCREEN. PROVIDE PULL STRING FOR <br />ALL CONDUITS. COORDINATE CONDUIT CONNECTION FOR LOW VOLTAGE CONTROLLER WITH AV <br />VENDOR. <br />PROVIDE (2) 1-1/4" CONDUITS FROM AV 119 TO EACH ACCESS PANEL. PROVIDE PULL STRING FOR <br />ALL CONDUITS. <br />PROVIDE (1) 1" CONDUIT FROM AV 119 TO FIRST SPEAKER IN EACH ROW. PROVIDE PULL STRING FOR <br />ALL CONDUITS. <br />MS CEILING MOUNTED MOTION SENSOR PROVIDE (1) 3/4" CONDUIT FROM TO NEAREST ACCESSIBLE CEILING. PROVIDE PULL STRING FOR ALL CONDUITS <br />1423 <br />A <br />C <br />B <br />1423 <br />A <br />C <br />SHEET NUMBER <br />TITLE <br />Approved <br />Checked <br />Drawn <br />Job Number <br />ISSUE CHART <br />CONSULTANTS <br />KEYPLAN <br />PROJECT <br />B <br />FIRM CERTIFICATION C.A #6057 <br />ERIK S WALKER P.E: #63929 <br />JOHN MOUDLER P.E: #33200 <br />CARLOS E. JIMENEZ P.E: #47923 <br />RICARDO DURAN P.E: #64768 <br />GLEN R. SEILER P.E: #83347 <br />BR+A CONSULTING ENGINEERS <br />2600 DOUGLAS ROAD, SUITE 1100 <br />CORAL GABLES, FL 33134 <br />THORNTON TOMASETTI <br />101 NE THIRD AVENUE, SUITE 1170 <br />FORT LAUDERDALE, FL 3330` <br />f.954.903.9300 <br />f 954.903 9301 <br />ESI CONSULTING ENGINEERS, INC <br />1315 NW 98TH CT. <br />UNIT 15, DORAL, FL 33172 <br />t. 305.418.9177 <br />t 305.418.9178 <br />HVAC <br />STRUCTURAL ENGINEERS <br />ELECTRICAL + PLUMBING <br />INMAN FOODSERICE GROUP <br />1330 CORAL WAY <br />SUITE 310 <br />MIAMI, FL 33145 <br />FOOD SERVICE <br />PE <br />R <br />M <br />I <br />T <br /> <br />S <br />E <br />T <br /> <br />1 <br />2 <br />. <br />0 <br />6 <br />. <br />1 <br />8 <br />1 2 /4 /2 0 1 8 8 :0 7 :1 7 A M <br />C :\_R e v i t \T E C H - G A T E W A Y - v 2 0 1 8 _a v i l l a n u e v a C B Y X V .r v t <br />AV00-01 <br />AV LEGEND <br />JJP <br />AMV <br />810495.000 <br />JJP <br />SIB -GATEWAY <br />PARK <br />Copyright © 2018 Perkins+Will <br />PROJECT ADDRESS: <br />151 Sunny Isles Blvd <br />Sunny Isles Beach, FL <br />33160 <br />2800 Ponce De Leon Blvd <br />Suite 1300 <br />Coral Gables, FL 33134 <br />t 305.569.1333 <br />f 305.569.1334 <br />www.perkinswill.com <br />NO.ISSUE DATE <br />PERMIT SET 12.06.2018