SCALE:N.T.S.
<br />DUCT PENETRATION CONSTRUCTION DETAIL
<br />GYPBOARD PARTITION MASONRY PARTITION
<br />GYP BOARD WALL
<br />CONSTRUCTION
<br />MASONRY WALL
<br />CONSTRUCTION
<br />ACOUSTICAL SEALANT
<br />SHEET METAL
<br />ENCLOSURE
<br />PACK W/ FIBERGLASS
<br />INSULATION (3# TO 6#
<br />DENSITY).
<br />REF: $M15723 SCALE:N.T.S.
<br />TYPICAL 90 DEG. DUCT TAP
<br />WITH DAMPER BLADE DETAIL
<br />CLINCH EDGES
<br />BRANCH DUCT
<br />AIR FLOW
<br />TRUNK DUCT
<br />45 DEGREE ANGLE
<br />PROVIDE OPPOSED BLADE DAMPER AT ALL
<br />LOW PRESSURE TAPS (DOWNSTREAM OF
<br />VAV BOXES, EXHAUST & O/A DUCTS).
<br />REF: $M15705
<br />SCALE:
<br />SCALE:
<br />SCALE:N.T.S.
<br />ROUND DUCT TAKE-OFF DETAIL
<br />AIR FLOW
<br />SPIN-IN FITTING WITH DAMPER, 45°
<br />EXTRACTOR AND LOCKING
<br />QUADRANT.
<br />FLEXIBLE CONNECTION
<br />REF: $M15703
<br />SCALE:N.T.S.
<br />FLEXIBLE DUCT CONNECTION DETAIL
<br />AIR FLOW
<br />DIFFUSER
<br />LOW VELOCITY SUPPLY AIR DUCT
<br />(SEE PLAN VIEW)
<br />INSULATED FLEXIBLE DUCT
<br />4" TO 6" HIGH METAL COLLAR ROUND
<br />DUCT, WITH 1-1/2" LBS/1" THICK, MFR.
<br />OWEN-CORNINGS, DUCT WRAP
<br />INSULATION, TO PERMIT FLEXIBLE DUCT
<br />CONN. AND OBD INSTALLATION
<br />ATTACH COLLAR TO DIFFUSER NECK
<br />W/ SCREWS 4" OC. SEAL JOINT W/
<br />DUCT SEALER AND TAPE.
<br />MANUAL OPPOSED
<br />BLADE DAMPER
<br />SEAL JOINT WITH
<br />DUCT SEALER &
<br />TAPE.
<br />REF: $M15709A SCALE:N.T.S.
<br />FLEXIBLE DUCT CONNECTION DETAIL
<br />AIR FLOW
<br />LOW VELOCITY
<br />SUPPLY AIR DUCT
<br />(SEE PLAN VIEW)
<br />SPIN-IN FITTING WITH
<br />EXTRACTOR AND
<br />QUADRANT DAMPER
<br />INSULATED FLEX. DUCT
<br />4" TO 6" HIGH METAL COLLAR
<br />ROUND DUCT, WITH 1 1/2 " LBS/IN
<br />THICK, MFR. OWEN-CORNINGS,
<br />DUCTWRAP INSULATION, TO
<br />PERMIT FLEXIBLE DUCT
<br />CONNECTION AND OBD
<br />INSTALLATION
<br />ATTACH COLLAR TO DIFFUSER
<br />NECK W/ SCREWS 4" O/C SEAL
<br />JOINT W/ DUCT SEALER AND TAPE.
<br />TO DIFFUSER
<br />SPIN-IN FITING WITH
<br />EXTRACTOR AND
<br />QUADRANT DAMPER
<br />MAKE TAP AT SIDE OR
<br />BOTTOM AS SHOWN ON
<br />PLANS
<br />SEAL JOINT WITH DUCT
<br />SEALER & TAPE
<br />DIFFUSER
<br />REF: $M15709B
<br />SPECIFIED
<br />DUCT SIZE
<br />SCALE:N.T.S.
<br />ROOF DUCT PENETRATION DETAIL
<br />(B)
<br />STANDARD DUCT
<br />CONSTRUCTION SEAMS
<br />WATERTIGHT SEAL
<br />FLASHING
<br />ROOFING
<br />DUCT INSULATION
<br />METAL FLASHING
<br />SHOULD EXTEND 4" MIN.
<br />BELOW TOP OF CURB
<br />FOR DETAIL B
<br />REF: $M15720C
<br />REF: $M15810A SCALE:N.T.S.
<br />DAMPER CONTROL SYSTEM
<br />BOWDEN CABLE REMOTE
<br />NOTES :
<br />1. COORDINATE EXACT LOCATION OF CEILING MOUNTED CONCEALED REGULATOR WITH ARCHITECT PRIOR TO
<br />INSTALLATION.
<br />2. THE 270-896 BOWDEN CABLE CONTROL SYSTEM IS DESIGNED TO BE IMBEDDED IN THE CEILING FLUSH WITH
<br />THE FINISHED SURFACE.
<br />3. CABLE SHALL CONSIST OF BOWDEN CABLE 0.054" STAINLESS STEEL CONTROL WIRE ENCAPSULATED IN 1/16"
<br />FLEXIBLE GALVANIZED SPIRAL WIRE SHEATH.
<br />4. LOCKING RACK AND PINION GEAR DRIVE SHALL BE CONSTRUCTED OF 14 GAUGE STEEL AND SHALL BE USED
<br />TO CONVERT ROTARY MOTION INTO PUSH-PULL MOTION.
<br />5. CONTROL SHAFT SHALL BE "D"-STYLE FLATTENED 1/4" DIAMETER WITH 265° ROTATION PROVIDING 1-1/2"
<br />LINEAR TRAVEL CAPABILITY.
<br />ROUND DAMPER
<br />FLEXIBLE CASING
<br />AND WIRE (50'-0"
<br />MAXIMUM)
<br />RIGID DUCTWORK
<br />FLEXIBLE DUCTWORK
<br />RACK & PINION
<br />OPERATOR
<br />MOUNTING BRACKET
<br />SOCKET WRENCH
<br />CEILING DIFFUSER
<br />7/8" THREADED CAP, TAMPER
<br />PROOF OPTIONAL
<br />CONCEALED REGULATOR KIT
<br />3 3/4"
<br />3 3/4"
<br />2 1/4
<br />3 3/8
<br />2 4" W ATERP RO O F DUCT
<br />6"6"
<br />A
<br />B
<br />1" AIR GAP
<br />UNIT TYPE A B
<br />DRAW THRU 2" PLUS X X
<br />BLOW THRU 1" MIN 2X
<br />WHERE "X" = STATIC PRESSURE IN PAN.
<br />D1 D2
<br />D5 ELBOWS VANE CONSTRUCTION DETAILS
<br />N.T.S.
<br />D8
<br />TYPICAL AHU CONDENSATE
<br />DRAIN CONNECTION DETAIL
<br />N.T.S.
<br />D7
<br />D9 D10 D11
<br />D16
<br />SCALE:N.T.S.
<br />DUCT SUPPORT DETAIL
<br />SCALE:N.T.S.
<br />OUTSIDE AIR INTAKE DETAIL
<br />SCALE:N.T.S.
<br />BOWDEN CABLE
<br />MANUAL VOLUME DAMPER REMOTE CENTER
<br />SCALE:N.T.S.
<br />PENETRATION DETAIL
<br />ROOF DUCT (INSULATED)
<br />SCALE:N.T.S.
<br />CEILING DIFFUSER INSTALLATION DETAIL
<br />SCALE:N.T.S.
<br />PENETRATION DETAIL
<br />ROOF DUCT (UNINSULATED)
<br />SCALE:N.T.S.
<br />EXHAUST FAN ROOF MOUNTING DETAIL
<br />UPBLAST
<br />SERIES FANSDOWNBLAST
<br />SERIES FANS
<br /> CONCRETE DECK ANCHORING
<br />3/8" S.S. HILTI KWIK BOLT 3
<br />EXPANSION ANCHORS
<br />MIN. 2.50" ENGAGEMENT
<br />SEE TABLE FOR QTY.
<br />(5" MIN. EDGE DISTANCE)
<br />2000 MIN. PSI
<br />CONCRETE
<br />ROOF CURB
<br />NOA RATED ROOF CURB,
<br />18 GA. MIN.; 24" TALL MAX.
<br />WELDED CONSTRUCTION
<br />CURB CORNER
<br />ANCHOR DETAIL
<br />CURB TO DECK MOUNTING
<br />GREENHECK UNIT SIZE
<br />CONCRETE ANCHORING
<br />NO. OF FASTENERS PER
<br />SIDE
<br />STEEL DECK ANCHORING
<br />NO. OF FASTENERS PER
<br />SIDE
<br />CUE / CUBE < 161
<br />G / GB < 141 2 2
<br />CUE / CUBE > 161
<br />G / GB > 141 3 3
<br />FASTENERS NEED TO BE LOCATED ON 2 OPPOSITE ENDS OF FAN CURB.
<br />FAN TO CURB MOUNTING
<br />GREENHECK UNIT SIZE FASTENERS PER SIDE
<br />CUE-060 THRU HP-161/HP, CUBE-098 THRU HP-161/HP/XP
<br />S-CUBE-141 THRU HP-161/HP, G-060 THRU 141, GB-071 THRU HP-161/HP 3
<br />CUE-180/HP-200, CUBE-180 THRU HP-240/HP/XP,
<br />S-CUBE-200 THRU 240, G-060 THRU 150, GB-180 THRU HP-240/HP 5
<br />CUBE-300/HP/XP, S-CUBE-300, GB-260-300/HP 9
<br />FASTENERS ON EACH SIDE OF THE FAN ARE TO BE INSTALLED WITH ONE FASTENER 4 INCHES FROM EACH EDGE
<br />AND ONE FASTENER CENTERED. THE FASTENERS ARE TO BE EQUALLY SPACED.5/16 INCH SELF-DRILLING SCREWS.
<br />FRONT VIEW
<br />TYPICAL ELBOW
<br />SIDE VIEW
<br />2-1/4" R
<br />45°
<br />2-1/4"
<br />4-1/2" R
<br />45°
<br />2-1/4"
<br />3-1/4"
<br />2" R
<br />DEPTH (D)
<br />WIDTH (W)
<br />45°45°
<br />1" R
<br />1-1/8" 1-1/8"
<br />2-1/8"
<br />NOTES
<br />1. ALL SQUARE OR RECTANGULAR ELBOWS SHALL HAVE ONE OF THE
<br />TWO TYPES OF TURNING VANES SHOWN ABOVE. SINGLE VANE
<br />ELBOWS WILL NOT BE PERMITTED.
<br />2. VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
<br />RECOMMENDED BY SMACNA.
<br />3. ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR
<br />EXHAUST OR RETURN DUCT MAY BE MADE RADIUS ELBOWS
<br />PROVIDED SPACE PERMITS RADIUS INSTALLATION.
<br />4. ALL SQUARE OR RECTANGULAR ELBOWS SHOWN ON PLANS FOR
<br />SUPPLY DUCT MAY BE MADE RADIUS ELBOWS PROVIDED SPACE
<br />PERMITS RADIUS INSTAL- LATION AND/OR THERE ISN'T AN OUTLET
<br />OR TAKE-OFF WITHIN 5D ON THE DOWNSTREAM SIDE OF THE
<br />ELBOW.
<br />SMALL DOUBLE VANE ELBOW USE FOR ELBOWS BELOW
<br />36" IN WIDTH AND ANY DEPTH
<br />LARGE DOUBLE VANE ELBOW USE FOR ELBOWS 36" 0R
<br />WIDER AND ANY DEPTH
<br />UNION
<br />DRAIN PAN
<br />AHU
<br />THREADED CAP WITH
<br />PERFORATION ON TOP
<br />DRAIN LINE SHALL BE AT LEAST THE
<br />SAME SIZE AS THE NIPPLE ON THE
<br />DRAIN PAN
<br />PITCH DOWN
<br />TOWARD DRAIN
<br />NOTES :
<br />1. FIRE RATED PACKING SHALL BE U.L. SYSTEM C-AJ-1015.
<br />2. SLOPE PIPE @ 1/4" PER FOOT.
<br />3. PROVIDE SHIELDING OVER CONDENSATE PIPING WHERE SUBJECT TO
<br />DAMAGE.
<br />4. SECURE NEW CONDENSATE DRAIN PIPING TO FLOOR WITH COPPER
<br />BRACKETS OR CLAMPS (USE NON-FERROUS FASTENERS).
<br />5. CONDENSATE LINE SHALL BE INSULATED WITH 1" ARMFLEX. PROVIDE
<br />PROTECTIVE ALUMINUM JACKETING TO PROTECT AGAINST DAMAGE.
<br />CLEAN-OUT (TYP.)
<br />CONCRETE ANCHORS
<br />CONCRETE ANCHORS
<br />(TYPICAL)
<br />STRAP SPACED AS PER
<br />SMACNA STANDARDS,
<br />SEE SPECIFICATIONS
<br />SECTION 15815
<br />WASHER MAY BE OMITTED WITH
<br />100 LBS. (45 KG) MAX LOAD ON
<br />22 GA. (0.85 mm) STRAP WHEN
<br />FOLDED
<br />DO NOT BEND STRAP AT
<br />90° BEND UNDER LOAD EXPANSION
<br />SHIELDS
<br />EXPANSION NAIL
<br />WASHER
<br />PROVIDE GASKET AT
<br />CONNECTION BETWEEN
<br />DUCTWORK AND LOUVER
<br />OUTSIDE AIR LOUVER W/
<br />VERTICAL BLADES SEE
<br />ARCH. DWGS. FOR
<br />DETAILS
<br />WALL
<br />BIRDSCREEN
<br />DUCT INSULATION, SEE
<br />SPECIFICATIONS FOR
<br />DETAILS
<br />INSULATION
<br />D4D3
<br />D6
<br />TO CONTROL
<br />DAMPER
<br />MODEL
<br />270-896C
<br />PLASTIC CAP
<br />"U" BRACKET
<br />SUPPORT
<br />STEEL PIPE
<br />CEILING7/8"∅ CAP
<br />WEATHERPROOF DUCTWORK,
<br />SEE MECH SPECS FOR
<br />INSULATION REQUIREMENTS
<br />CURB TOP FLASHING WITH DRIP
<br />EDGE & WEATHERPROOF COLLAR
<br />BY G.C.
<br />12" ALUMINUM COUNTER -
<br />FLASHING SKIRT BY MECH
<br />CONTRACTOR, SEALED TO
<br />DUCT "S" SLIP BY MECH
<br />CONTRACTOR
<br />CURB FURNISHED BY MECH
<br />CONTRACTOR, INSTALLED,
<br />FLASHED & SEALED BY G.C.
<br />MECH CONTRACTOR TO PACK
<br />VOIDS BETWEEN DUCT &
<br />STRUCTURAL OPENING (TYP), SEE
<br />SPECIFICATION
<br />SILICONE CAULKING
<br />BY MECH
<br />CONTRACTOR (TYP)
<br />2" LINER BEGINS
<br />1" LINER ENDS
<br />AIR FLOW
<br />EXTRACTOR
<br />ROUND SHEET METAL
<br />COLLAR
<br />SECURE FLEX. WITH METAL
<br />BANDS
<br />4" TO 6" HIGH ROUND
<br />METAL DUCT COLLAR WITH
<br />11/2 LBS. 1" THICK DUCT
<br />WRAP INSULATION
<br />SEAL INSULATION TO
<br />DUCT AND CEILING WITH
<br />VAPOR BARRIER TAPE
<br />SUPPLY
<br />DUCT
<br />INSULATED FLEXIBLE
<br />ROUND, SEE
<br />SPECIFICATIONS
<br />OPPOSSED BLADE
<br />DAMPER, SEE
<br />SPECIFICATIONS
<br />CEILING
<br />DIFFUSER GRID BAR
<br />WEATHERPROOF DUCTWORK,
<br />SEE MECH SPECS FOR
<br />INSULATION REQUIREMENTS
<br />CURB TOP FLASHING WITH DRIP
<br />EDGE & WEATHERPROOF COLLAR
<br />BY G.C.
<br />12" ALUMINUM COUNTER -
<br />FLASHING SKIRT BY MECH
<br />CONTRACTOR, SEALED TO
<br />DUCT "S" SLIP BY MECH
<br />CONTRACTOR
<br />CURB FURNISHED BY MECH
<br />CONTRACTOR, INSTALLED,
<br />FLASHED & SEALED BY G.C.
<br />MECH CONTRACTOR TO PACK
<br />VOIDS BETWEEN DUCT &
<br />STRUCTURAL OPENING (TYP), SEE
<br />SPECIFICATION
<br />SILICONE CAULKING
<br />BY MECH
<br />CONTRACTOR (TYP)
<br />D12 D13 D14 D15
<br />REF: $M15618
<br />REF: $M15737REF: $M15736A
<br />REF: $M15810REF: $M15721B REF: $M15726REF: $M15721A
<br />1423
<br />A
<br />C
<br />B
<br />1423
<br />A
<br />C
<br />SHEET NUMBER
<br />TITLE
<br />Approved
<br />Checked
<br />Drawn
<br />Job Number
<br />ISSUE CHART
<br />CONSULTANTS
<br />KEYPLAN
<br />PROJECT
<br />B
<br />PE
<br />R
<br />M
<br />I
<br />T
<br />
<br />S
<br />E
<br />T
<br />
<br />1
<br />2
<br />.
<br />0
<br />6
<br />.
<br />1
<br />8
<br />FIRM CERTIFICATION C.A #6057
<br />JOHN MOUDLER P.E: #33200
<br />CARLOS E. JIMENEZ P.E: #47923
<br />JOHN J. PETERS RCDD: #193108R
<br />BR+A CONSULTING ENGINEERS
<br />2600 DOUGLAS ROAD, SUITE 1100
<br />CORAL GABLES, FL 33134
<br />THORNTON TOMASETTI
<br />101 NE THIRD AVENUE, SUITE 1170
<br />FORT LAUDERDALE, FL 3330`
<br />f.954.903.9300
<br />f 954.903 9301
<br />ESI CONSULTING ENGINEERS, INC
<br />1315 NW 98TH CT, UNIT 15
<br />DORAL, FL 33172
<br />t. 305.418.9177 f 305.418.9178
<br />HVAC
<br />STRUCTURAL ENGINEERS
<br />ELECTRICAL + PLUMBING
<br />INMAN FOODSERICE GROUP
<br />1330 CORAL WAY
<br />SUITE 310
<br />MIAMI, FL 33145
<br />FOOD SERVICE
<br />FIRM CERTIFICATION C.A. #26243
<br />IGOR F. GONZALEZ P.E. #56098
<br />1 2 /4 /2 0 1 8 6 :1 4 :0 1 P M
<br />D :\U s e r s \K a r i n \D o c u m e n t s \C 0 2 0 3 2 1 1 8 -M E C H _R 1 8 _k a r i n c @ e s i c o n s u l t .c o m .r v t
<br />M40-01
<br />MECHANICAL DETAILS
<br />Checker
<br />Author
<br />810495.000
<br />Approver
<br />SIB -GATEWAY
<br />PARK
<br />PROJECT ADDRESS:
<br />151 Sunny Isles Blvd
<br />Sunny Isles Beach, FL
<br />33160
<br />2800 Ponce De Leon Blvd,
<br />Suite 1300,
<br />Coral Gables, FL 3313
<br />t 305.569.1333
<br />f 305.569.1334
<br />www.perkinswill.com
<br />MARK ISSUE DATE