GF
<br />I
<br />G
<br />F
<br />I
<br />GFIGFI GFIGFI GFIGFI GFIGFI
<br />FDFD
<br />FD
<br />K L M
<br />1
<br />1.2
<br />30A/2P208V/F/NEMA 4XSS
<br />CU-5A
<br />PNL "A"-34,36
<br />PNL "A"-35
<br />CU-2
<br />PNL "A"-30,32
<br />3#8, 1#10 G IN 3/4"C
<br />WP
<br />F G H I J K L
<br />2.2
<br />3
<br />4
<br />67
<br />CCWDP-1,3,5
<br />60A/3PH/208V/F/NEMA 4XSS
<br />200A/3PH/208V/F/
<br />NEMA 4XSS
<br />200A/3PH/
<br />208V/F/
<br />NEMA 4XSS
<br />CCWDP-2,4,6
<br />100A/3PH/208V/F/NE
<br />MA 4XSS60A/3PH/208V/F/NEMA 4XSS
<br />1
<br />60A/3PH/208V/F/NEMA 4XSS
<br />CCWDP-7,9,11
<br />60A/3PH/208V/F/NEMA 4XSS
<br />CCWDP-8,10,12
<br />CCEDP-1,3,5
<br />60A/3PH/208V/F/NEMA
<br />4XSS
<br />CCEDP-7,9,11
<br />CCEDP-13,15
<br />30A/1PH/208V/F/NEMA
<br />4XSS
<br />RTU-5
<br />RTU-4
<br />EF-2
<br />RTU-6
<br />RTU-7RTU-3
<br />RTU-2RTU-1
<br />67
<br />CU-8
<br />CCER-7
<br />7
<br />CU-5B
<br />CCWDP-14,16
<br />30A/1PH/208V/F/NE
<br />MA 4XSS
<br />CCWDP-13,15,17
<br />CCEDP-14,16
<br />30A/1PH/208V/F/NEMA 4XSS
<br />3#8, 1#10G, 3/4"C
<br />3#1, 1#8G, 1-1/2"C
<br />3#8, 1#10G, 3/4"C 3#6, 1#8G, 1"C 3#10, 1#10G, 3/4"C
<br />3#8, 1#10G, 3/4"C
<br />3#2/0, 1#6G, 2"C
<br />3#2/0, 1#6G, 2"C
<br />3#8, 1#10G, 3/4"C
<br />CU-1
<br />3#10, 1#10G, 3/4"C
<br />COORDINATE VFDS LOCATIONS
<br />WITH MECHANICAL DRAWINGS
<br />FIELD COORDINATE EXACT
<br />DISCONNECT LOCATION
<br />(TYPICAL)
<br />WP WP WP WP
<br />EF-1
<br />1
<br />30A/1P/120V/F/NEMA 4XSS
<br />30A/3P/208V/F/NEMA 4XSS
<br />KEF-1
<br />CCWDP-22,24,26
<br />CCWR-10
<br />CCWR-67
<br />1
<br />1 1
<br />2
<br />CCEDP-2,4,6
<br />1
<br />12
<br />2
<br />2
<br />2
<br />1 PROVIDE RECEPTACLES WITHIN 25FT OF ALL MECHANICAL EQUIPMENT ON THE ROOF. CONNECT ANY ADDITIONAL THAT MAY BE REQUIRED TO THIS CIRCUIT.
<br />POWER KEYNOTES:
<br />2 MOUNT DISCONNECTS TO ENSURE NEC REQUIRED CLEARANCES ARE MET, TYPICAL. COORDINATE LOCATIONS OF VFDS WITH VENDORS. 1
<br />H I J K L
<br />2
<br />1423
<br />A
<br />C
<br />B
<br />1423
<br />A
<br />C
<br />SHEET NUMBER
<br />TITLE
<br />Approved
<br />Checked
<br />Drawn
<br />Job Number
<br />ISSUE CHART
<br />CONSULTANTS
<br />KEYPLAN
<br />PROJECT
<br />B
<br />FIRM CERTIFICATION C.A #6057
<br />JOHN MOULDER P.E: #33200
<br />CARLOS E. JIMENEZ P.E: #47923
<br />JOHN J. PETERS RCDD #193108R
<br />BR+A CONSULTING ENGINEERS
<br />2600 DOUGLAS ROAD, SUITE 1100
<br />CORAL GABLES, FL 33134
<br />t. 305.529.1515
<br />THORNTON TOMASETTI
<br />101 NE THIRD AVENUE, SUITE 1170
<br />FORT LAUDERDALE, FL 3330`
<br />f.954.903.9300
<br />f 954.903 9301
<br />ESI CONSULTING ENGINEERS, INC
<br />1315 NW 98TH CT.
<br />UNIT 15, DORAL, FL 33172
<br />t. 305.418.9177 t 305.418.9178
<br />HVAC
<br />STRUCTURAL ENGINEERS
<br />ELEC + PLUM + FPRO + TECH
<br />INMAN FOODSERICE GROUP
<br />1330 CORAL WAY
<br />SUITE 310
<br />MIAMI, FL 33145
<br />FOOD SERVICE
<br />PE
<br />R
<br />M
<br />I
<br />T
<br />
<br />S
<br />E
<br />T
<br />
<br />1
<br />2
<br />.
<br />0
<br />6
<br />.
<br />1
<br />8
<br />FIRM CERTIFICATION C.A #26243
<br />IGOR F. GONZALEZ P.E: #56098
<br />1 /1 5 /2 0 1 9 2 :2 0 :3 0 P M
<br />C :\_R e v i t \E L E C - G A T E W A Y - v 2 0 1 8 _g s e i l e r A 6 Y M L .r v t
<br />E11-01
<br />LEVEL 02 -ELECTRICAL
<br />POWER PLAN
<br />Checker
<br />Author
<br />810495.000
<br />Approver
<br />SIB -GATEWAY
<br />PARK
<br />Copyright © 2018 Perkins+Will
<br />PROJECT ADDRESS:
<br />151 Sunny Isles Blvd
<br />Sunny Isles Beach, FL
<br />33160
<br />2800 Ponce De Leon Blvd
<br />Suite 1300
<br />Coral Gables, FL 33134
<br />t 305.569.1333
<br />f 305.569.1334
<br />www.perkinswill.com
<br />1/8" = 1'-0"1 LEVEL 02 - Power - Elevator Area
<br />1/8" = 1'-0"2 LEVEL 02 - Power - Parapet AREA
<br />1/8" = 1'-0"3 LEVEL 04 - Power
<br />NO.ISSUE DATE
<br />PERMIT SET 12.06.2018
<br />1 Revision 1 01.09.2019
<br />1
<br />2
|