Laserfiche WebLink
SAMSON OCEANFRONT PARK <br />CITY OF SUNNY ISLES <br />TECHNICAL SPECIFICATIONS <br /> <br /> <br />HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT 15061-7 <br /> <br />install the following types: <br />1. Steel-Pipe-Covering Protection Saddles (MSS Type 39): To fill interior voids with insulation <br />that matches adjoining insulation. <br />2. Protection Shields (MSS Type 40): Of length recommended in writing by manufacturer to <br />prevent crushing insulation. <br />3. Thermal-Hanger Shield Inserts: For supporting insulated pipe. <br /> <br />O. Spring Hangers and Supports: Unless otherwise indicated and except as specified in piping system <br />Sections, install the following types: <br />1. Spring Cushions (MSS Type 48): For light loads if vertical movement does not exceed 1-1/4 <br />inches <br />2. Spring-Cushion Roll Hangers (MSS Type 49): For equipping Type 41, roll hanger with <br />. <br />springs. <br />3. Variable-Spring Base Supports (MSS Type 52): Preset to indicated load and limit variability <br />factor to 25 percent to allow expansion and contraction of piping system from base support. <br /> <br />P. Comply with MSS SP-69 for trapeze pipe-hanger selections and applications that are not specified <br />in piping system Sections. <br /> <br />Q. Use powder-actuated fasteners or mechanical-expansion anchors instead of building attachments <br />where required in concrete construction. <br /> <br />R. Use pipe positioning systems in pipe spaces behind plumbing fixtures to support supply and waste <br />piping for plumbing fixtures. <br />END OF SECTION