Laserfiche WebLink
t <br />PART 3 - EXECUTION <br />3.01 CONDUIT INSTALLATION <br />A. Where conduits enter or leave all outlet boxes, cabinets safety switches, tap <br />boxes, motor controllers, etc., other than those having threaded hubs, a <br />standard lock nut shall be used on the outside of the box. Busings 1 -inch and <br />larger shall be of an approved insulated type. <br />B. During construction, all installed raceways shall be temporarily plugged or <br />' otherwise protected from the entrance of moisture, dirt, trash, plaster, <br />moisture, etc., through neglect of the CONTRACTOR to so protect them, shall <br />be replaced by the CONTRACTOR without additional expense to the Owner. <br />No kinked, clogged or deformed raceways will be permitted on the job. <br />Raceways shall be cut to proper length so that ends will fit accurately in the <br />outlets. Where raceways cross building expansion joints, a suitable raceway <br />expansion fitting shall be used. <br />' C. Size of raceway shall not be less than NEC requirements, but in no case shall <br />be less than indicated on the Drawings. Combining of circuits, other than <br />detailed, will not be permitted. The CONTRACTOR shall install larger size <br />raceways than detailed where there is excessive length of unbroken run or <br />excessive number of bends. <br />' D. Bends in metallic raceways shall be made while "cold" and in no case shall the <br />raceways be heated. Raceways shall not be bent through more than 900. The <br />radius of bends shall not be less than six (6) times the internal diameter of the <br />raceway. Not more than four (4) (equivalent 901) bends will be permitted <br />between outlets, the bends at the outlets being counted. <br />E. Raceways shall be properly aligned, grouped and supported. Exposed <br />raceways shall be installed at the right angles to or parallel to the principal <br />structural members. Concealed raceways, unless otherwise indicated, may <br />take the most direct route between outlets. Raceways shall be firmly held in <br />place. Raceways shall run to avoid trapping wherever possible. Where areas <br />are indicated for future openings, foundations, etc., all raceways shall be run <br />around such areas. The CONTRACTOR shall provide necessary inserts in <br />poured concrete areas and shall furnish and install all necessary sleeves <br />through walls, floors and roofs for passage of raceways. Sleeves through <br />roofs and /or exterior walls shall be properly sealed by the CONTRACTOR <br />against entrance of moisture, etc., into the building. Where necessary repairs <br />to the building structure using material in no way inferior to that originally <br />installed and using labor skilled in the trades involved. <br />1 09/03 16050 -9 03- 4138.A -R <br />