Laserfiche WebLink
C. The ground plane shall consist of a minimum of 2 -5/8" x 10' copper ground <br />rods spaced at least 10' apart. Rods and system ground shall be connected <br />with a #6 copper ground to the service entrance ground. The ground <br />resistance shall be tested and additional rods or plates added to achieve a dry <br />season resistance not exceeding 5 ohms. <br />3.05 CONDUCTOR COLOR CODING <br />A. All conductors shall be color coded as specified hereinafter. Color coding shall <br />be by means of colored insulation material, colored braid or jacket over the <br />insulation, or by means of suitable colored permanent, non -aging insulation <br />tape equal to Scotch #471 or "Texcel 98" applied to conductors at each <br />outlet, cabinet or junction point. <br />B. The following system of color coding shall be strictly adhered to: <br />1. Ground leads, green. <br />2. Grounded neutral leads, white. <br />3. Ungrounded phase wires of a 120/208 volt, 3- phase, 4 -wire system, <br />black, red and blue. <br />4. All control leads, other than line connected "hot" leads, shall be yellow, <br />orange and brown and /or I.P.C.E.A. standard control cable coding <br />provided method of identification is different from method used on <br />power conductors. <br />C. The color coding assigned to each phase wire shall be consistently followed <br />throughout the Work. <br />� oso, <br />END OF SECTION <br />16050-11 <br />03- 4138.A -R <br />