Laserfiche WebLink
C. Size of raceway shall not be less than NEC requirements, but in no case shall <br />be less than indicated on the Drawings. Combining of circuits, other than <br />detailed, will not be permitted. The CONTRACTOR shall install larger size <br />' raceways than detailed where there is excessive length of unbroken run or <br />excessive number of bends. <br />D. Bends in metallic raceways shall be made while "cold" and in no case shall the <br />raceways be heated. Raceways shall not be bent through more than 900. <br />The radius of bends shall not be less than six (6) times the internal diameter of <br />the raceway. Not more than four (4) (equivalent 901) bends will be permitted <br />between outlets, the bends at the outlets being counted. <br />E. Raceways shall be properly aligned, grouped and supported. Exposed <br />raceways shall be installed at the right angles to or parallel to the principal <br />structural members. Concealed raceways, unless otherwise indicated, may <br />take the most direct route between outlets. Raceways shall be firmly held in <br />place. Raceways shall run to avoid trapping wherever possible. Where areas <br />are indicated for future openings, foundations, etc., all raceways shall be run <br />around such areas. The CONTRACTOR shall provide necessary inserts in <br />poured concrete areas and shall furnish and install all necessary sleeves <br />' through walls, floors and roofs for passage of raceways. Sleeves through <br />roofs and /or exterior walls shall be properly sealed by the CONTRACTOR <br />against entrance of moisture, etc., into the building. Where necessary repairs <br />a to the building structure using material in no way inferior to that originally <br />installed and using labor skilled in the trades involved. <br />1 3.02 BOXES <br />A. Install all outlet boxes, tap, junction or pull boxes, device boxes, etc., <br />necessary for the complete installation as indicated on the Drawing and /or <br />specified herein. All raceways entering boxes shall be mechanically and <br />' electrically secure. Open knockouts or holes in boxes shall be plugged with <br />suitable blanking devices. Boxes shall be cleared of all plaster, dirt, trash, etc., <br />before the installation of any wiring devices and /or before the installation of <br />cover plates. <br />B. All pull boxes shall be precast concrete with traffic rated covers. Boxes shall <br />be sized as per the NEC. Precast boxes shall be manufactured by Brooks <br />Products Co., or approved equal. <br />' 3.03 TERMINATIONS & SPLICES <br />A. Splices, taps and attachments of fittings and lugs shall be electrically and <br />mechanically secure. Approved solderless lugs and connectors shall be used <br />1 04/04 16050 -10 03 -4115 <br />